Deemed-to-Satisfy Provision · NCC 2022 Volume One

J3D6 Wall thermal breaks of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building · NCC 2019: J0.5

Open J3D6 on NCC Online ↗

(1) A metal-framed wall that forms part of the building envelope must have a thermal break, consisting of a material with an R-Value of not less than R0.2, installed at all points of contact between the external cladding and the metal frame if the wall—

does not have a wall lining or has a wall lining that is fixed directly to the same metal frame; and

is clad with weatherboards, fibre-cement or the like, or metal sheeting fixed to a metal frame.

(2) The requirements of (1) do not apply to walls constructed using insulated sandwich panels.

Changed in NCC 2025. See NCC 2025 Volume One J3D6, or show what changed.

(1) A metal-framed wall that forms part of the building envelope must have a thermal break, consisting of a material with an R-Value of not less than R0.2, installed at all points of contact between the external cladding and the metal frame if the wall — does not have a wall lining or This clause has a wall lining that is fixed directly to the same metal frame; and is clad with weatherboards, fibre-cement or the like, or metal sheeting fixed to a metal frame. (2) The requirements of (1) do not apply to walls constructed using insulated sandwich panels. deliberately been left blank.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J3D6? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →

Defined terms used