New South Wales variation · NCC 2022 Volume One

NSW C2D11 Fire hazard properties

Part C2 Fire resistance and stability · varies C2D11 Fire hazard properties

Open on NCC Online ↗

Delete clause C2D11 and insert NSW C2D11 as follows:

(1) The fire hazard properties of the following internal linings, materials and assemblies within a Class 2 to 9 building must comply with Specification 7:

Floor linings and floor coverings.

Wall linings and ceiling linings.

Air-handling ductwork.

Lift cars.

In Class 9b buildings used as—

an entertainment venue, a material used to cover closed back upholstered seats; and

a public hall or the like, a proscenium curtain required by Specification 32.

Escalators, moving walkways and non-required non fire-isolated stairways or pedestrian ramps subject to Specification 14.

Sarking-type materials.

Attachments to floors, ceilings, internal walls, common walls, fire walls and to internal linings of external walls.

Other materials including insulation materials other than sarking-type materials.

(2) Paint or fire-retardant coatings must not be used in order to make a material comply with a required fire hazard property, except in respect of a material referred to in NSW Specification 7, NSW Table S7C7 and to which Notes 4 and 5 are applicable.

(3) The requirements of (1) do not apply to a material or assembly if it is—

plaster, cement render, concrete, terrazzo, ceramic tile or the like; or

a fire-protective covering; or

a timber-framed window; or

a solid timber handrail or skirting; or

a timber-faced door; or

an electrical switch, socket-outlet, cover plate or the like; or

a material used for—

a roof insulating material applied in continuous contact with a substrate; or

an adhesive; or

a damp-proof course, flashing, caulking, sealing, ground moisture barrier, or the like; or

a paint, varnish, lacquer or similar finish, other than nitro-cellulose lacquer; or

a clear or translucent roof light of glass fibre-reinforced polyester if—

the roof in which it is installed forms part of a single storey building required to be Type C construction; and

the material is used as part of the roof covering; and

it is not closer than 1.5 m from another roof light of the same type; and

each roof light is not more than 14 m2 in area; and

the area of the roof lights per 70 m2 of roof surface is not more than 14 m2; or

a face plate or neck adaptor of supply and return air outlets of an air handling system; or

a face plate or diffuser plate of light fitting and emergency exit signs and associated electrical wiring and electrical components; or

a joinery unit, cupboard, shelving, or the like; or

an attached non-building fixture and fitting such as—

a curtain, blind, or similar decor, other than—

a proscenium curtain required by Specification 32; or

in a Class 9b building used as an entertainment venue, a material regulated under NSW Table S7C7; and

a whiteboard, window treatment or the like; or

timber treads, risers, landings and associated supporting framework installed in accordance with D3D30 where the Spread-of-Flame Index and the Smoke-Developed Index of the timber does not exceed 9 and 8 respectively; or

any other material that does not significantly increase the hazards of fire.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One NSW C2D11.