D3D30 Timber stairways: Concession
Part D3 Construction of exits · NCC 2019: D2.25
(1) Notwithstanding D3D3(a), timber treads, risers, landings and associated supporting framework within a required fire-isolated stairway or fire-isolated passageway may be constructed from fire-protected timber in accordance with C2D13—
if the timber—
has a finished thickness of not less than 44 mm; and
has an average density of not less than 800 kg/m3 at a moisture content of 12%; and
subject to—
the building being protected throughout by a sprinkler system (other than a FPAA101D system) complying with Specification 17 which extends to within the fire-isolated enclosure; and
fire protection being provided to the underside of stair flights and landings located immediately above a landing level which—
is at or near the level of egress; or
provides direct access to a carpark.
(2) Fire protection required by (1) must be not less than one layer of 13 mm fire-protective grade plasterboard fixed in accordance with the system requirements for a fire-protective covering.