NSW E2D10 Buildings not more than 25 m in effective height: large isolated buildings subject to C3D4
Part E2 Smoke hazard management · varies E2D10 Buildings not more than 25 m in effective height: large isolated buildings subject to C3D4
Delete clause E2D10 and insert NSW E2D10 as follows:
(1) In a Class 5, 6, 7, 8 or 9 building of not more than 25 m in effective height, and which exceeds 18 000 m2 in floor area or 108 000 m3 in volume, the building must be provided with—
if the ceiling height of the fire compartment is not more than 12 m—
an automatic smoke exhaust system in accordance with Specification 21; or
automaticsmoke-and-heat vents in accordance with Specification 22; or
if the ceiling height of the fire compartment is more than 12 m, an automatic smoke exhaust system in accordance with Specification 21.
(2) For the purposes of (1), reference to ‘the building’ being provided with specified measures, means to the nominated classes within the building.
Notes
Refer to E2D14 and E2D15 for specific provisions applicable to a Class 6 building or part of a building (in a fire compartment having a floor area of more than 2000 m2).
Refer to NSW E2D16 to NSW E2D19 for specific provisions applicable to a Class 9b building or part of a building.
Refer to E2D5 and E2D8 where a Class 5, 6, 7b, 8 and 9b building contains a Class 2, 3 or 4 part.