NSW J4D6 Walls and glazing
Part J4 Building fabric · varies J4D6 Walls and glazing
Delete clause J4D6 and insert NSW J4D6 as follows:
(1) The Total System U-Value of wall-glazing construction, including wall-glazing construction which wholly or partly forms the envelope internally, must not be greater than—
for a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area, U2.0; and
for a Class 3 or 9c building or a Class 9a ward area—
in climate zones 1, 3, 4, 6 or 7, U1.1; or
in climate zones 2 or 5, U2.0; or
in climate zone 8, U0.9.
(2) The Total System U-Value of display glazing must not be greater than U5.8.
(3) The Total System U-Value of wall-glazing construction must be calculated in accordance with Specification 37.
(4) Wall components of a wall-glazing construction must achieve a minimum Total R-Value of—
where the wall is less than 80% of the area of the wall-glazing construction, R1.0; or
where the wall is 80% or more of the area of the wall-glazing construction, the value specified in NSW Table J4D6a.
(5) The solar admittance of externally facing wall-glazing construction, excluding wall-glazing construction which is wholly internal, must not be greater than—
for a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area, the values specified in NSW Table J4D6b; and
for a Class 3 or 9c building or a Class 9a ward area, the values specified in NSW Table J4D6c.
(6) The solar admittance of a wall-glazing construction must be calculated in accordance with Specification 37.
(7) The Total system SHGC of display glazing must not be greater than 0.81 divided by the applicable shading factor specified in S37C7.
Insert NSW table (NSW J4D6a) J4D6 as follows:
NSW Table NSW J4D6a: Minimum wall Total R-Value - Wall area 80% or more of wall-glazing construction area
Climate zone
Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area
Class 3 or 9c building or Class 9a ward area
1
2.4
3.3
2
1.4
1.4
3
1.4
3.3
4
1.4
2.8
5
1.4
1.4
6
1.4
2.8
7
1.4
2.8
8
1.4
3.8
Insert NSW table (J4D6b) J4D6 as follows:
NSW Table J4D6b: Maximum wall-glazing construction solar admittance - Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
Climate zone
Eastern aspect solar admittance
Northern aspect solar admittance
Southern aspect solar admittance
Western aspect solar admittance
1
0.12
0.12
0.12
0.12
2
0.13
0.13
0.13
0.13
3
0.16
0.16
0.16
0.16
4
0.13
0.13
0.13
0.13
5
0.13
0.13
0.13
0.13
6
0.13
0.13
0.13
0.13
7
0.13
0.13
0.13
0.13
8
0.2
0.2
0.42
0.36
Table J4D6c Maximum wall-glazing construction solar admittance - Class 3 or 9c building or Class 9a ward area
Climate zone
Eastern aspect solar admittance
Northern aspect solar admittance
Southern aspect solar admittance
Western aspect solar admittance
1
0.07
0.07
0.10
0.07
2
0.10
0.10
0.10
0.10
3
0.07
0.07
0.07
0.07
4
0.07
0.07
0.07
0.07
5
0.10
0.10
0.10
0.10
6
0.07
0.07
0.07
0.07
7
0.07
0.07
0.08
0.07
8
0.08
0.08
0.08
0.08