F7D6 Sound insulation rating of walls
Part F7 Sound transmission and insulation · NCC 2019: NT F5.5 and NT Table F5.5, F5.5
(1) A wall in a Class 2 or 3 building must—
have an Rw + Ctr (airborne) not less than 50, if it separates sole-occupancy units; and
have an Rw (airborne) not less than 50, if it separates a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby or the like, or parts of a different classification; and
comply with F7D4(2) if it separates—
a bathroom, sanitary compartment, laundry or kitchen in one sole-occupancy unit from a habitable room (other than a kitchen) in an adjoining unit; or
a sole-occupancy unit from a plant room or lift shaft.
(2) A door may be incorporated in a wall in a Class 2 or 3 building that separates a sole-occupancy unit from a stairway, public corridor, public lobby or the like, provided the door assembly has an Rw not less than 30.
(3) A wall in a Class 9c building must have an Rw not less than 45 if it separates—
sole-occupancy units; or
a sole-occupancy unit from a kitchen, bathroom, sanitary compartment (not being an associated ensuite), laundry, plant room or utilities room.
(4) In addition to (3), a wall separating a sole-occupancy unit in a Class 9c building from a kitchen or laundry must comply with F7D4(2).
(5) Where a wall required to have sound insulation has a floor above, the wall must continue to—
the underside of the floor above; or
a ceiling that provides the sound insulation required for the wall.
(6) Where a wall required to have sound insulation has a roof above, the wall must continue to—
the underside of the roof above; or
a ceiling that provides the sound insulation required for the wall.