S31C10 Smoke exhaust system
Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 3.4
A smoke exhaust system serving an atrium must be designed on the basis of—
the sprinkler system limiting the size of a fire to—
a heat output of 1.5 MW and perimeter of 7.5 m if a Class 2, 3, 5 or 9 part of the building is open to the atrium; or
a heat output of 5 MW and perimeter of 12 m if a Class 6, 7 or 8 part of the building is open to the atrium; and
a smoke plume reaching a level 3 m above the highest storey having a path of travel to a required exit along a balcony bounding the atrium well, and not less than—
12 m above the floor of an atrium or the floor of the highest storey where the bounding wall is set back more than 3.5 m from the atrium well if a Class 2, 3, 5 or 9 part of the building is open to the atrium; or
20 m above the floor of an atrium or the floor of the highest storey where the bounding construction is set back more than 3.5 m from the atrium well if a Class 6, 7 or 8 part of the building is open to the atrium; and
the smoke exhaust system discharging smoke at a rate of not less than that shown in Figure S31C10 for the appropriate height of smoke plume and fire size—
from the top of the atrium; or
horizontally, where calculations of wind velocity induced pressure profiles for the building verify that the exhaust system will operate effectively for all wind directions.
Figure S31C10 Smoke exhaust rate