Specification clause · NCC 2025 Volume One

S31C10 Smoke exhaust system

Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 3.4

Open S31C10 on NCC Online ↗

A smoke exhaust system serving an atrium must be designed on the basis of—

the sprinkler system limiting the size of a fire to—

a heat output of 1.5 MW and perimeter of 7.5 m if a Class 2, 3, 5 or 9 part of the building is open to the atrium; or

a heat output of 5 MW and perimeter of 12 m if a Class 6, 7 or 8 part of the building is open to the atrium; and

a smoke plume reaching a level 3 m above the highest storey having a path of travel to a required exit along a balcony bounding the atrium well, and not less than—

12 m above the floor of an atrium or the floor of the highest storey where the bounding wall is set back more than 3.5 m from the atrium well if a Class 2, 3, 5 or 9 part of the building is open to the atrium; or

20 m above the floor of an atrium or the floor of the highest storey where the bounding construction is set back more than 3.5 m from the atrium well if a Class 6, 7 or 8 part of the building is open to the atrium; and

the smoke exhaust system discharging smoke at a rate of not less than that shown in Figure S31C10 for the appropriate height of smoke plume and fire size—

from the top of the atrium; or

horizontally, where calculations of wind velocity induced pressure profiles for the building verify that the exhaust system will operate effectively for all wind directions.

Figure S31C10 Smoke exhaust rate

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S31C10.

Defined terms used