Specification clause · NCC 2022 Volume One
S31C9 Activation of smoke control system
Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 3.3
(1) The smoke control system must be activated by—
operation of an automatic fire alarm; or
operation of the sprinkler system; or
a manual start switch.
(2) All controls for the smoke control system must be located—
in the fire control room; or
in the emergency control centre (if any); or
adjacent to the sprinkler control valves; or
incorporated in the Fire Indicator Panel.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S31C9.