Specification clause · NCC 2022 Volume One

S31C14 Make-up air supply

Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 3.8

Open S31C14 on NCC Online ↗

(1) Uniformly distributed make-up air must be provided to the atrium exhaust system from—

outside the atrium at or near the lowest storey level; and

relief air from non-fire storeys.

(2) A discharge volume sufficient to maintain a velocity of not less than 0.1 m/s towards the atrium well must be provided on all storeys where the bounding wall is set back from the atrium well.

(3) The requirements of (1)(a) are satisfied if make-up air is provided to the atrium exhaust system in such a manner as to prevent, as far as possible, disturbance of the smoke layer due to turbulence created by the incoming air, through—

openings directly from the outside air to the atrium and located as close as practicable to the lowest level of the atrium; or

ducts from the outside air to the atrium which deliver air as close as practicable to the lowest level of the atrium and, where passing through any other fire compartment having an FRL of at least 60/60/60; or

a combination of (a) or (b).

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S31C14.