S6C4 Walls of shafts and fire-isolated exits generally
Specification 6 Structural tests for lightweight construction · NCC 2019: Spec C1.8: 3.2
A wall of lightweight construction that is required to be fire-resisting and which bounds a lift shaft, stair shaft, or service shaft, fire-isolated passageway or fire-isolated ramp must be subjected to the following tests and must fulfil the following criteria:
The materials tests of S6C10(a) and the criteria of S6C11(a).
A static test by the imposition of a uniformly distributed load of 0.35 kPa (or its equivalent) in accordance with S6C10(b) and the damage and deflection criteria of S6C11(b) and (c) respectively.
A dynamic test by the fall of the impact bag through a height of 150 mm in accordance with S6C10(c) and the damage and deflection criteria of S6C11(b) and (d) respectively.
The surface indentation test of S6C10(d) and the surface indentation criterion of S6C11(e).