South Australia variation · NCC 2022 Volume One
SA D2D3 Number of exits required
Part D2 Provision for escape · varies D2D3 Number of exits required
Delete subclause D2D3(2) and insert SA D2D3(2) as follows:
(2) Class 2 to 8 buildings — In addition to any horizontal exit, not less than 2 exits must be provided from the following:
Each storey if the building has an effective height of more than 25 m.
A Class 2 or 3 building subject to C2D6.
A storage shed in a bulk grain storage facility if the distance of travel to an exit is more than 150 m.
The gallery level in a cell type silo in a bulk grain storage facility.
Not in NCC 2025. No SA D2D3 in NCC 2025 Volume One.