D2D3 Number of exits required
Part D2 Provision for escape · NCC 2019: D1.2
(1) All buildings — Every building must have at least one exit from each storey.
(2) Class 2 to 8 buildings —
In addition to any horizontal exit, not less than 2 exits must be provided from the following:
Each storey if the building has an effective height of more than 25 m.
A Class 2 or 3 building subject to C2D6.
The requirements of (a)(i) do not apply to a part of a storey that—
is provided with direct egress to a road or open space; and
satisfies D2D5 by the provision of 1 exit.
(3) Basements — In addition to any horizontal exit, not less than 2 exits must be provided from any storey if egress from that storey involves a vertical rise within the building of more than 1.5 m, unless—
the floor area of the storey is not more than 50 m²; and
the distance of travel from any point on the floor to a single exit is not more than 20 m.
(4) Class 9 buildings —
In addition to any horizontal exit, not less than 2 exits must be provided from the following:
Each storey if the building has a rise in storeys of more than 6 or an effective height of more than 25 m.
Any storey which includes a patient care area in a Class 9a health-care building.
Any storey that contains sleeping areas in a Class 9c building.
Any storey used as a Class 9b early childhood centre, or any Class 9b early childhood centre which forms part of a storey.
Each storey in a primary or secondary school with a rise in storeys of 2 or more.
Any storey or mezzanine that accommodates more than 50 persons, calculated under D2D18.
The requirements of (a) do not apply to a part of a storey that—
is a plant room, machinery room, storeroom, lift-machine room or the like; and
is provided with direct egress to a road, open space or a fire-isolated exit complying with D2D12(2); and
satisfies D2D5 by the provision of 1 exit.
(5) Exits from Class 9c buildings and patient care areas in Class 9a health-care buildings — In a Class 9a health-care building and a Class 9c building, at least one exit must be provided from every part of a storey which has been divided into fire compartments in accordance with C3D3 or C3D6.
(6) Exits in open spectator stands — In an open spectator stand containing more than one tier of seating, every tier must have not less than 2 stairways or ramps, each forming part of the path of travel to not less than 2 exits.
(7) Access to exits — Without passing through another sole-occupancy unit every occupant of a storey or part of a storey must have access to—
an exit; or
at least 2 exits if 2 or more exits are required.
State and territory variations all clauses side by side →
- NSW Replaced Delete subclause D2D3(4) and insert NSW D2D3(4) as follows: (4) Class 9 buildings— In addition to any horizontal exit, not less…
- SA Replaced Delete subclause D2D3(2) and insert SA D2D3(2) as follows: (2) Class 2 to 8 buildings — In addition to any horizontal exit, not…
Clauses referred to
- C2D6 Two storey Class 2, 3 or 9c buildings
- D2D5 Exit travel distances
- D2D18 Number of persons accommodated
- C3D3 General floor area and volume limitations