Table · NCC 2022 Volume One
Table D3D14 Riser and going dimensions
| Stairway location | Riser (R) | Going (G)Note 3 | Quantity (2R + G) | |||
|---|---|---|---|---|---|---|
| Max | Min | Max | Min | Max | Min | |
| Public | 190 | 115 | 355 | 250 | 700 | 550 |
| Private Note 1 | 190 | 115 | 355 | 240 | 700 | 550 |
Table Notes
Private stairways are—
stairways in a sole-occupancy unit in a Class 2 building or Class 4 part of a building; and
in any building, stairways which are not part of a required exit and to which the public do not normally have access.
Going and riser dimensions must be measured in accordance with Figure D3D14.
The going in tapered treads (except winders in lieu of a quarter or half landing) in a curved or spiral stairway is measured—
270 mm in from the outer side of the unobstructed width of the stairway if the stairway is less than 1 m wide (applicable to a non-required stairway only); and
270 mm from each side of the unobstructed width of the stairway if the stairway is 1 m wide or more.
Table for D3D14 Goings and risers
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table D3D14.