Deemed-to-Satisfy Provision · NCC 2022 Volume One

D3D12 Fire-isolated passageways

Part D3 Construction of exits · NCC 2019: D2.11

Open D3D12 on NCC Online ↗

(1) The enclosing construction of a fire-isolated passageway must have an FRL when tested for a fire outside the passageway in another part of the building of—

if the passageway discharges from a fire-isolated stairway or ramp — not less than that required for the stairway or ramp shaft; or

in any other case — not less than 60/60/60.

(2) Notwithstanding (1)(b), the top construction of a fire-isolated passageway need not have an FRL if the walls of the fire-isolated passageway extend to the underside of—

a non-combustible roof covering; or

a ceiling having a resistance to the incipient spread of fire of not less than 60 minutes separating the roof space or ceiling space in all areas surrounding the passageway within the fire compartment.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One D3D12.
Can't meet D3D12? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P9. Start a Performance Solution →