J3D3 Reducing heating and cooling loads of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building using house energy rating software
Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building · NCC 2019: J0.2
(1) The sole-occupancy units of a Class 2 building or a Class 4 part of a building must—
for reducing the heating or cooling loads—
collectively achieve an average energy rating of not less than 7 stars, including the separate heating and cooling load limits; and
individually achieve an energy rating of not less than 6 stars, including the separate heating and cooling load limits; and
for thermal breaks, comply with J3D5 and J3D6; and
for compensating for a loss of ceiling insulation, other than where the house energy rating software has compensated for a loss of ceiling insulation, comply with Table J3D7w; and
for general thermal construction, comply with J4D3; and
for floor edge insulation, comply with J3D10(3), J3D10(5) and J3D10(6); and
for building sealing, comply with Part J5.
(2) Energy ratings referred to in (1)(a)(i) and (ii) must be achieved using—
house energy rating software; and
the load limits specified in the ABCB Standard for NatHERS Heating and Cooling Load Limits.
Changed in NCC 2025. See NCC 2025 Volume One J3D3, or show what changed.
(1) The sole-occupancy units of a Class 2 building or a Class 4 part of a building must — for reducing … and cooling load limits; and for thermal breaks, comply with J3D5 and J3D6; J3D5; and for compensating for a loss of ceiling insulation, other … with Table J3D7w; and for general thermal construction, comply with J4D3; J4D3(1) to J4D3(4); and for floor edge insulation, comply with J3D10(3), J3D10(5) and … the ABCB Standard for NatHERS Heating and Cooling Load Limits.
Removed words are struck through; added words are highlighted. Comparison of the text only.
State and territory variations all clauses side by side →
Clauses referred to
- J3D5 Roof thermal breaks of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building
- J3D6 Wall thermal breaks of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building
- J4D3 Thermal construction — general
- J3D10 Floors of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building