Table J3D7j Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 4

Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Open Table J3D7j on NCC Online ↗
Reflective insulation under-roof≤ 0.64
Yes2.0
No2.5

Table Notes

SA = solar absorptance.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

Table for J3D7 Roofs and ceilings of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D7j.