Table · NCC 2022 Volume One
Table J3D7k Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 4
| Roof ventilation | Reflective insulation under- roof | Under-roof insulation R-Value | SA ≤ 0.23 | SA > 0.23 to ≤ 0.64 |
|---|---|---|---|---|
| Vented | Yes | < 0.5 | 3.0 | 3.5 |
| ≥ 0.5 | 3.0 | 3.0 | ||
| No | Any | 3.5 | ||
| Standard | Yes | Any | 3.0 | |
| No | < 0.5 | 3.5 | ||
| ≥ 0.5 | 3.0 |
Table Notes
SA = solar absorptance.
A roof is considered ‘vented’ if it—
has one wind-driven roof ventilator per 50 m2 of ceiling area with gable, eave or ridge vents; or
has one powered roof ventilator per 200 m2 of ceiling area with gable, eave or ridge vents; or
is a tiled roof without sarking-type material at roof level.
If a roof is not ‘vented’, it is a ‘standard’ roof.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D7k.