Table · NCC 2022 Volume One

Table J3D7k Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 4

Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Open Table J3D7k on NCC Online ↗
Roof ventilationReflective insulation under- roofUnder-roof insulation R-ValueSA ≤ 0.23SA > 0.23 to ≤ 0.64
VentedYes< 0.53.03.5
≥ 0.53.03.0
NoAny3.5
StandardYesAny3.0
No< 0.53.5
≥ 0.53.0

Table Notes

SA = solar absorptance.

A roof is considered ‘vented’ if it—

has one wind-driven roof ventilator per 50 m2 of ceiling area with gable, eave or ridge vents; or

has one powered roof ventilator per 200 m2 of ceiling area with gable, eave or ridge vents; or

is a tiled roof without sarking-type material at roof level.

If a roof is not ‘vented’, it is a ‘standard’ roof.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

Table for J3D7 Roofs and ceilings of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D7k.