Table · NCC 2022 Volume One
Table J3D7l Timber-framed flat, skillion or cathedral timber roof — minimum R-Value for ceiling insulation: climate zone 4
| Reflective insulation under-roof | SA ≤ 0.64 |
|---|---|
| Yes | 3.0 |
| No | 3.5 |
Table Notes
SA = solar absorptance.
The R-Value can be achieved by installing insulation under the roof or on top of the ceiling or a combination of both.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D7l.