Table · NCC 2022 Volume One

Table J4D6b Maximum wall-glazing construction solar admittance - Class 2 common area, Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area

Part J4 Building fabric

Open Table J4D6b on NCC Online ↗
Climate zoneEastern aspect solar admittanceNorthern aspect solar admittanceSouthern aspect solar admittanceWestern aspect solar admittance
10.120.120.120.12
20.130.130.130.13
30.160.160.160.16
40.130.130.130.13
50.130.130.130.13
60.130.130.130.13
70.130.130.130.13
80.20.20.420.36

Table for J4D6 Walls and glazing

Changed in NCC 2025. See NCC 2025 Volume One Table J4D6b, or show what changed.

Climate zone | Eastern aspect solar admittance Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area | Northern aspect solar admittance | Southern aspect solar admittance | Western aspect solar admittance Class 3 or 9c building or Class 9a ward area 1 | 0.12 3.0 | 0.12 | 0.12 | 0.12 4.0 2 | 0.13 1.0 | 0.13 | 0.13 | 0.13 1.0 3 | 0.16 2.2 | 0.16 | 0.16 | 0.16 2.4 4 | 0.13 2.0 | 0.13 | 0.13 | 0.13 1.9 5 | 0.13 1.0 | 0.13 | 0.13 | 0.13 1.0 6 | 0.13 1.2 | 0.13 | 0.13 | 0.13 1.0 7 | 0.13 2.2 | 0.13 | 0.13 | 0.13 2.2 8 | 0.2 3.6 | 0.2 | 0.42 | 0.36 3.6

Removed words are struck through; added words are highlighted. Comparison of the text only.