Table · NCC 2022 Volume One
Table J4D6b Maximum wall-glazing construction solar admittance - Class 2 common area, Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
| Climate zone | Eastern aspect solar admittance | Northern aspect solar admittance | Southern aspect solar admittance | Western aspect solar admittance |
|---|---|---|---|---|
| 1 | 0.12 | 0.12 | 0.12 | 0.12 |
| 2 | 0.13 | 0.13 | 0.13 | 0.13 |
| 3 | 0.16 | 0.16 | 0.16 | 0.16 |
| 4 | 0.13 | 0.13 | 0.13 | 0.13 |
| 5 | 0.13 | 0.13 | 0.13 | 0.13 |
| 6 | 0.13 | 0.13 | 0.13 | 0.13 |
| 7 | 0.13 | 0.13 | 0.13 | 0.13 |
| 8 | 0.2 | 0.2 | 0.42 | 0.36 |
Table for J4D6 Walls and glazing
Changed in NCC 2025. See NCC 2025 Volume One Table J4D6b, or show what changed.
Climate zone | Eastern aspect solar admittance Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area | Northern aspect solar admittance | Southern aspect solar admittance | Western aspect solar admittance Class 3 or 9c building or Class 9a ward area 1 | 0.12 3.0 | 0.12 | 0.12 | 0.12 4.0 2 | 0.13 1.0 | 0.13 | 0.13 | 0.13 1.0 3 | 0.16 2.2 | 0.16 | 0.16 | 0.16 2.4 4 | 0.13 2.0 | 0.13 | 0.13 | 0.13 1.9 5 | 0.13 1.0 | 0.13 | 0.13 | 0.13 1.0 6 | 0.13 1.2 | 0.13 | 0.13 | 0.13 1.0 7 | 0.13 2.2 | 0.13 | 0.13 | 0.13 2.2 8 | 0.2 3.6 | 0.2 | 0.42 | 0.36 3.6
Removed words are struck through; added words are highlighted. Comparison of the text only.