Table J6D11b Minimum energy efficiency ratio for refrigerant chillers – Option 2
Part J6 Air-conditioning and ventilation
| Chiller type | Full load operation (Wr/Winput power) | Integrated part load (Wr/Winput power) |
|---|---|---|
| Air-cooled chiller with a capacity ≤ 528 kWr | 2.866 | 4.669 |
| Air-cooled chiller with a capacity > 528 kWr | 2.866 | 4.758 |
| Water-cooled positive displacement chiller with a capacity ≤ 264 kWr | 4.513 | 7.041 |
| Water-cooled positive displacement chiller with a capacity > 264 kWr but ≤ 528 kWr | 4.694 | 7.184 |
| Water-cooled positive displacement chiller with a capacity > 528 kWr but ≤ 1055 kWr | 5.177 | 8.001 |
| Water-cooled positive displacement chiller with a capacity > 1055 kWr but ≤ 2110 kWr | 5.633 | 8.586 |
| Water-cooled positive displacement chiller with a capacity > 2110 kWr | 6.018 | 9.264 |
| Water-cooled centrifugal chiller with a capacity ≤ 528 kWr | 5.065 | 8.001 |
| Water-cooled centrifugal chiller with a capacity > 528 kWr but ≤ 1055 kWr | 5.544 | 8.001 |
| Water-cooled centrifugal chiller with a capacity > 1055 kWr but ≤ 1407 kWr | 5.917 | 9.027 |
| Water-cooled centrifugal chiller with a capacity > 1407 kWr | 6.018 | 9.264 |
Table for J6D11 Refrigerant chillers
Changed in NCC 2025. See NCC 2025 Volume One Table J6D11b, or show what changed.
Chiller type Climate zone | Full Design load operation (Wr/Winput power) not greater than 450 kW | Integrated part Design load (Wr/Winput power) Air-cooled chiller with a capacity ≤ 528 kWr greater than 450 kW to 900 kW | 2.866 Design load greater than 900 kW to 2,400 kW | 4.669 Air-cooled chiller with a capacity > 528 kWr Design load greater than 2,400 kW 1 | 2.866 5.2 | 4.758 Water-cooled positive displacement chiller with a capacity ≤ 264 kWr 6.2 | 4.513 6.4 | 7.041 Water-cooled positive displacement chiller with a capacity > 264 kWr but ≤ 528 kWr 6.8 2 | 4.694 5.7 | 7.184 Water-cooled positive displacement chiller with a capacity > 528 kWr but ≤ 1055 kWr 7.0 | 5.177 7.8 | 8.001 Water-cooled positive displacement chiller with a capacity > 1055 kWr but ≤ 2110 kWr 8.4 3 | 5.633 6.1 | 8.586 Water-cooled positive displacement chiller with a capacity > 2110 kWr 8.2 | 6.018 9.5 | 9.264 Water-cooled centrifugal chiller with a capacity ≤ 528 kWr 10.5 4 | 5.065 6.2 | 8.001 Water-cooled centrifugal chiller with a capacity > 528 kWr but ≤ 1055 kWr 8.1 | 5.544 9.4 | 8.001 Water-cooled centrifugal chiller with a capacity > 1055 kWr but ≤ 1407 kWr 10.7 5 | 5.917 5.9 | 9.027 Water-cooled centrifugal chiller with a capacity > 1407 kWr 7.2 | 6.018 8.1 | 9.264 9.2 6 | 6.3 | 8.3 | 9.5 | 10.7 7 | 6.2 | 8.2 | 9.4 | 10.9 8 | 6.4 | 9.0 | 10.6 | 12.8