Table · NCC 2022 Volume One

Table J6D11a Minimum energy efficiency ratio for refrigerant chillers – Option 1

Part J6 Air-conditioning and ventilation

Open Table J6D11a on NCC Online ↗
Chiller typeFull load operation (Wr/Winput power)Integrated part load (Wr/Winput power)
Air-cooled chiller with a capacity ≤ 528 kWr2.9854.048
Air-cooled chiller with a capacity > 528 kWr2.9854.137
Water-cooled positive displacement chiller with a capacity ≤ 264 kWr4.6945.867
Water-cooled positive displacement chiller with a capacity > 264 kWr but ≤ 528 kWr4.8896.286
Water-cooled positive displacement chiller with a capacity > 528 kWr but ≤ 1055 kWr5.3346.519
Water-cooled positive displacement chiller with a capacity > 1055 kWr but ≤ 2110 kWr5.8006.770
Water-cooled positive displacement chiller with a capacity > 2110 kWr6.2867.041
Water-cooled centrifugal chiller with a capacity ≤ 528 kWr5.7716.401
Water-cooled centrifugal chiller with a capacity > 528 kWr but ≤ 1055 kWr5.7716.519
Water-cooled centrifugal chiller with a capacity > 1055 kWr but ≤ 1407 kWr6.2866.770
Water-cooled centrifugal chiller with a capacity > 1407 kWr6.2867.041

Table for J6D11 Refrigerant chillers

Changed in NCC 2025. See NCC 2025 Volume One Table J6D11a, or show what changed.

Climate zone | Chiller type rated cooling capacity kW | Full load operation (Wr/Winput power) energy efficiency ratio | Integrated part load (Wr/Winput power) Air-cooled chiller with a capacity value 1, 2 | 0 to 250 | 5.0 | — 1, 2 | > 250 to ≤ 528 kWr 500 | 2.985 5.6 | 4.048 Air-cooled chiller with a capacity — 1, 2 | > 528 kWr 500 to ≤ 1,500 | 2.985 6.1 | 4.137 Water-cooled positive displacement chiller with a capacity — 1, 2 | > 1,500 | 6.5 | — 3 | 0 to 250 | 5.0 | 6.2 3 | > 250 to ≤ 264 kWr 500 | 4.694 5.8 | 5.867 Water-cooled positive displacement chiller with a capacity 8.3 3 | > 264 kWr but 500 to ≤ 528 kWr 1,500 | 4.889 6.0 | 6.286 Water-cooled positive displacement chiller with a capacity 10.4 3 | > 528 kWr but 1,500 | 6.3 | 11.4 4, 5, 6, 7 or 8 | 0 to 250 | 5.0 | 6.2 4, 5, 6, 7 or 8 | > 250 to ≤ 1055 kWr 500 | 5.334 5.5 | 6.519 Water-cooled positive displacement chiller with a capacity 8.3 4, 5, 6, 7 or 8 | > 1055 kWr but 500 to ≤ 2110 kWr 1,500 | 5.800 6.0 | 6.770 Water-cooled positive displacement chiller with a capacity 10.4 4, 5, 6, 7 or 8 | > 2110 kWr 1,500 | 6.286 6.3 | 7.041 Water-cooled centrifugal chiller with a capacity ≤ 528 kWr | 5.771 | 6.401 Water-cooled centrifugal chiller with a capacity > 528 kWr but ≤ 1055 kWr | 5.771 | 6.519 Water-cooled centrifugal chiller with a capacity > 1055 kWr but ≤ 1407 kWr | 6.286 | 6.770 Water-cooled centrifugal chiller with a capacity > 1407 kWr | 6.286 | 7.041 11.4

Removed words are struck through; added words are highlighted. Comparison of the text only.