J6D11 Refrigerant chillers
Part J6 Air-conditioning and ventilation · NCC 2019: J5.10
An air-conditioning system refrigerant chiller must comply with MEPS and the full load operation energy efficiency ratio and integrated part load energy efficiency ratio in Table J6D11a or Table J6D11b when determined in accordance with AHRI 551/591.
Table J6D11a Minimum energy efficiency ratio for refrigerant chillers – Option 1
Chiller type
Full load operation (Wr/Winput power)
Integrated part load (Wr/Winput power)
Air-cooled chiller with a capacity ≤ 528 kWr
2.985
4.048
Air-cooled chiller with a capacity > 528 kWr
2.985
4.137
Water-cooled positive displacement chiller with a capacity ≤ 264 kWr
4.694
5.867
Water-cooled positive displacement chiller with a capacity > 264 kWr but ≤ 528 kWr
4.889
6.286
Water-cooled positive displacement chiller with a capacity > 528 kWr but ≤ 1055 kWr
5.334
6.519
Water-cooled positive displacement chiller with a capacity > 1055 kWr but ≤ 2110 kWr
5.800
6.770
Water-cooled positive displacement chiller with a capacity > 2110 kWr
6.286
7.041
Water-cooled centrifugal chiller with a capacity ≤ 528 kWr
5.771
6.401
Water-cooled centrifugal chiller with a capacity > 528 kWr but ≤ 1055 kWr
5.771
6.519
Water-cooled centrifugal chiller with a capacity > 1055 kWr but ≤ 1407 kWr
6.286
6.770
Water-cooled centrifugal chiller with a capacity > 1407 kWr
6.286
7.041
Table J6D11b Minimum energy efficiency ratio for refrigerant chillers – Option 2
Chiller type
Full load operation (Wr/Winput power)
Integrated part load (Wr/Winput power)
Air-cooled chiller with a capacity ≤ 528 kWr
2.866
4.669
Air-cooled chiller with a capacity > 528 kWr
2.866
4.758
Water-cooled positive displacement chiller with a capacity ≤ 264 kWr
4.513
7.041
Water-cooled positive displacement chiller with a capacity > 264 kWr but ≤ 528 kWr
4.694
7.184
Water-cooled positive displacement chiller with a capacity > 528 kWr but ≤ 1055 kWr
5.177
8.001
Water-cooled positive displacement chiller with a capacity > 1055 kWr but ≤ 2110 kWr
5.633
8.586
Water-cooled positive displacement chiller with a capacity > 2110 kWr
6.018
9.264
Water-cooled centrifugal chiller with a capacity ≤ 528 kWr
5.065
8.001
Water-cooled centrifugal chiller with a capacity > 528 kWr but ≤ 1055 kWr
5.544
8.001
Water-cooled centrifugal chiller with a capacity > 1055 kWr but ≤ 1407 kWr
5.917
9.027
Water-cooled centrifugal chiller with a capacity > 1407 kWr
6.018
9.264
Tables
- Table J6D11a Minimum energy efficiency ratio for refrigerant chillers – Option 1
- Table J6D11b Minimum energy efficiency ratio for refrigerant chillers – Option 2
Changed in NCC 2025. See NCC 2025 Volume One J6D11, or show what changed.
An air-conditioning system refrigerant (1) Refrigerant chillers must — individually, comply with (2); or collectively, comply with (3). (2) When assessed in accordance with AHRI 551/591, a chiller must comply with MEPS — where air-cooled — in climate zones 1 or 3, achieve a full load operation energy efficiency ratio of not less than 3.1; and the in climate zones 2, 4, 5, 6 or 7 achieve a full load operation energy efficiency ratio and an integrated part load value such that the sum of the two is not less than — 8.1, where the rated cooling capacity of the chiller is not greater than 550 kW; and 8.5, where the rated cooling capacity of the chiller is greater than 550 kW; and in climate zone 8, achieve an integrated part load value of not less than — 5.1, where the rated cooling capacity of the chiller is not greater than 550 kW; or 5.4, where the rated cooling capacity of the chiller is greater than 550 kW; and where water-cooled — in climate zones 1 or 2, achieve full load operation energy efficiency ratio of not less than the value specified in Table J6D11a J6D11a; and in climate zones 3 to 8, achieve a full load operation energy efficiency ratio and an integrated part load value such that the sum of the two is not less than the sum of the full load and integrated part load values specified in Table J6D11a, as applicable. (3) A connected group of one or Table J6D11b when more refrigerant chillers, used as part of an air-conditioning system, must achieve a climate specific part load value, determined in accordance with AHRI 551/591. Specification 47, greater than — the applicable value specified in Table J6D11b, where all chillers in the group are water-cooled; or the applicable value specified in Table J6D11c, where all chillers in the group are air-cooled; or the average of the applicable values specified in Table J6D11b and Table J6D11c weighted according to the total full-load capacity of the chillers, where the group has both water-cooled and air-cooled chillers. (4) The requirements of (1), (2) and (3) do not apply to — 4-pipe chillers; or air-source heat pump water heaters. Table J6D11a Minimum energy efficiency ratio or integrated part load value for water-cooled refrigerant chillers – Option 1 other than 4-pipe chillers Climate zone Chiller type rated cooling capacity kW Full load operation (Wr/Winput power) energy efficiency ratio Integrated part load (Wr/Winput power) Air-cooled chiller with a capacity value 1, 2 0 to 250 5.0 — 1, 2 > 250 to ≤ 528 kWr 2.985 4.048 Air-cooled chiller with a capacity 500 5.6 — 1, 2 > 528 kWr 2.985 4.137 Water-cooled positive displacement chiller with a capacity 500 to ≤ 264 kWr 4.694 5.867 Water-cooled positive displacement chiller with a capacity 1,500 6.1 — 1, 2 > 264 kWr but 1,500 6.5 — 3 0 to 250 5.0 6.2 3 > 250 to ≤ 528 kWr 4.889 6.286 Water-cooled positive displacement chiller with a capacity 500 5.8 8.3 3 > 528 kWr but 500 to ≤ 1055 kWr 5.334 6.519 Water-cooled positive displacement chiller with a capacity 1,500 6.0 10.4 3 > 1055 kWr but 1,500 6.3 11.4 4, 5, 6, 7 or 8 0 to 250 5.0 6.2 4, 5, 6, 7 or 8 > 250 to ≤ 2110 kWr 5.800 6.770 Water-cooled positive displacement chiller with a capacity 500 5.5 8.3 4, 5, 6, 7 or 8 > 2110 kWr 6.286 7.041 Water-cooled centrifugal chiller with a capacity 500 to ≤ 528 kWr 5.771 6.401 Water-cooled centrifugal chiller with a capacity 1,500 6.0 10.4 4, 5, 6, 7 or 8 > 528 kWr but ≤ 1055 kWr 5.771 6.519 Water-cooled centrifugal chiller with a capacity > 1055 kWr but ≤ 1407 kWr 6.286 6.770 Water-cooled centrifugal chiller with a capacity > 1407 kWr 6.286 7.041 1,500 6.3 11.4 Table J6D11b Minimum energy efficiency ratio for refrigerant chillers – Option 2 Chiller type Full load operation (Wr/Winput power) Integrated climate specific part load (Wr/Winput power) Air-cooled value for a connected group of water-cooled chiller with plant Climate zone Design load not greater than 450 kW Design load greater than 450 kW to 900 kW Design load greater than 900 kW to 2,400 kW Design load greater than 2,400 kW 1 5.2 6.2 6.4 6.8 2 5.7 7.0 7.8 8.4 3 6.1 8.2 9.5 10.5 4 6.2 8.1 9.4 10.7 5 5.9 7.2 8.1 9.2 6 6.3 8.3 9.5 10.7 7 6.2 8.2 9.4 10.9 8 6.4 9.0 10.6 12.8 Table J6D11c Minimum climate specific part load value for a capacity ≤ 528 kWr 2.866 4.669 Air-cooled connected group of air-cooled chiller with a capacity > 528 kWr 2.866 4.758 Water-cooled positive displacement chiller with a capacity ≤ 264 kWr 4.513 7.041 Water-cooled positive displacement chiller with a capacity > 264 kWr but ≤ 528 kWr 4.694 7.184 Water-cooled positive displacement chiller with a capacity > 528 kWr but ≤ 1055 kWr 5.177 8.001 Water-cooled positive displacement chiller with a capacity > 1055 kWr but ≤ 2110 kWr 5.633 8.586 Water-cooled positive displacement chiller with a capacity > 2110 kWr 6.018 9.264 Water-cooled centrifugal chiller with a capacity ≤ 528 kWr 5.065 8.001 Water-cooled centrifugal chiller with a capacity > 528 kWr but ≤ 1055 kWr 5.544 8.001 Water-cooled centrifugal chiller with a capacity > 1055 kWr but ≤ 1407 kWr 5.917 9.027 Water-cooled centrifugal chiller with a capacity > 1407 kWr 6.018 9.264 plant Climate zone Design load not greater than 900 kW Design load greater than 900 kW 1 4.1 3.9 2 4.8 4.5 3 4.3 4.1 4 4.9 4.5 5 5.1 4.8 6 5.4 5.0 7 5.2 4.9 8 5.6 5.5
Removed words are struck through; added words are highlighted. Comparison of the text only.