Table · NCC 2022 Volume One
Table J6D5e Maximum clean filter pressure drop
Part J6 Air-conditioning and ventilation
| Filter minimum efficiency reporting value | Maximum pressure drop (Pa) |
|---|---|
| 9 | 55 |
| 11 | 65 |
| 13 | 95 |
| 14 | 110 |
Table for J6D5 Fans and duct systems
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J6D5e.