J6D5 Fans and duct systems
Part J6 Air-conditioning and ventilation · NCC 2019: J5.4
(1) Fans, ductwork and duct components that form part of an air-conditioning system or mechanical ventilation system must—
separately comply with (2), (3), (4) and (5); or
achieve a fan motor input power per unit of flowrate lower than the fan motor input power per unit of flowrate achieved when applying (2), (3), (4) and (5) together.
(2) Fans:
Fans in systems that have a static pressure of not more than 200 Pa must have an efficiency at the full load operating point not less than the efficiency calculated with the following formula: [formula] In the formula at (a)—
[formula] = the minimum required system static efficiency for installation type A or C or the minimum required system total efficiency installation type B or D; and
[formula] = the static pressure of the system (Pa); and
[formula] = natural logarithm.
Fans in systems that have a static pressure above 200 Pa must have an efficiency at the full load operating point not less than the efficiency calculated with the following formula: [formula] In the formula at (c)—
[formula] = the minimum required system static efficiency for installation type A or C or the minimum required system total efficiency installation type B or D; and
[formula] = the motor input power of the fan (kW); and
[formula] = the minimum performance grade obtained from Table J6D5a; and
[formula] = regression coefficient a, obtained from Table J6D5b; and
[formula] = regression coefficient b, obtained from Table J6D5c; and
[formula] = natural logarithm.
The requirements of (a), (b), (c) and (d) do not apply to fans that need to be explosion proof.
(3) Ductwork:
The pressure drop in the index run across all straight sections of rigid ductwork and all sections of flexible ductwork must not exceed 1 Pa/m when averaged over the entire length of straight rigid duct and flexible duct. The pressure drop of flexible ductwork sections may be calculated as if the flexible ductwork is laid straight.
Flexible ductwork must not account for more than 6 m in length in any duct run.
The upstream connection to ductwork bends, elbows and tees in the index run must have an equivalent diameter to the connected duct.
Turning vanes must be included in all rigid ductwork elbows of 90° or more acute than 90° in the index run except where—
the inclusion of turning vanes presents a fouling risk; or
a long radius bend in accordance with AS 4254.2 is used.
(4) Ductwork components in the index run:
The pressure drop across a coil must not exceed the value specified in Table J6D5d.
A high efficiency particulate arrestance (HEPA) air filter must not exceed the higher of—
a pressure drop of 200 Pa when clean; or
the filter design pressure drop when clean at an air velocity of 1.5 m/s.
Any other air filter must not exceed—
the pressure drop specified in Table J6D5e when clean; or
the filter design pressure drop when clean at an air velocity of 2.5 m/s.
The pressure drop across intake louvres must not exceed the higher of—
for single stage louvres, 30 Pa; and
for two stage louvres, 60 Pa; and
for acoustic louvres, 50 Pa; and
for other non-weatherproof louvres, 30 Pa.
The pressure drop across a variable air volume box, with the damper in the fully open position, must not exceed—
for units with electric reheat, 100 Pa; and
for other units, 25 Pa not including coil pressure losses.
Rooftop cowls must not exceed a pressure drop of 30 Pa.
Attenuators must not exceed a pressure drop of 40 Pa.
Fire dampers must not exceed a pressure drop of 15 Pa when open.
Balancing and control dampers in the index run must not exceed a pressure drop of 25 Pa when in the fully open position.
Supply air diffusers and grilles must not exceed a pressure drop of 40 Pa.
Exhaust grilles must not exceed a pressure drop of 30 Pa.
Transfer ducts must not exceed a pressure drop of 12 Pa.
Door grilles must not exceed a pressure drop of 12 Pa.
Active chilled beams must not exceed a pressure drop of 150 Pa.
(5) The requirements of (1), (2), (3) and (4) do not apply to—
fans in unducted air-conditioning systems with a supply air capacity of less than 1000 L/s; and
smoke spill fans, except where also used for air-conditioning or ventilation; and
the power for process-related components; and
kitchen exhaust systems.
Table J6D5a Minimum fan performance grade
Fan type
Installation type A or C
Installation type B or D
Axial — as a component of an air handling unit or fan coil unit
46.0
51.5
Axial — other
42.0
61.0
Mixed flow — as a component of an air handling unit or fan coil unit
46.0
51.5
Mixed flow — other
52.5
65.0
Centrifugal forward — curved
46.0
51.5
Centrifugal radial bladed
46.0
51.5
Centrifugal backward-curved
64.0
64.0
Table Notes
Installation type A means an arrangement where the fan is installed with free inlet and outlet conditions.
Installation type B means an arrangement where the fan is installed with a free inlet and a duct at its outlet.
Installation type C means an arrangement where the fan is installed with a duct fitted to its inlet and with free outlet conditions.
Installation type D means an arrangement where the fan is installed with a duct fitted to its inlet and outlet.
Table J6D5b Fan regression coefficient a
Fan type
Fan motor input power < 10 kW
Fan motor input power ≥ 10 kW
Axial
2.74
0.78
Mixed flow
4.56
1.1
Centrifugal forward-curved
2.74
0.78
Centrifugal radial bladed
2.74
0.78
Centrifugal backward-curved
4.56
1.1
Table J6D5c Fan regression coefficient b
Fan type
Fan motor input power < 10 kW
Fan motor input power ≥ 10 kW
Axial
6.33
1.88
Mixed flow
10.5
2.6
Centrifugal forward-curved
6.33
1.88
Centrifugal radial bladed
6.33
1.88
Centrifugal backward-curved
10.5
2.6
Table J6D5d Maximum coil pressure drop
Number of rows
Maximum pressure drop (Pa)
1
30
2
50
4
90
6
130
8
175
10
220
Table J6D5e Maximum clean filter pressure drop
Filter minimum efficiency reporting value
Maximum pressure drop (Pa)
9
55
11
65
13
95
14
110
Tables
- Table J6D5a Minimum fan performance grade
- Table J6D5b Fan regression coefficient a
- Table J6D5c Fan regression coefficient b
- Table J6D5d Maximum coil pressure drop
- Table J6D5e Maximum clean filter pressure drop
Changed in NCC 2025. See NCC 2025 Volume One J6D5, or show what changed.
(1) Fans, ductwork and duct components that form part of an air-conditioning system or mechanical ventilation system must — separately comply with (2), (3), (4) and (5); (2) to (12); or achieve a fan motor input power per unit of … motor input power per unit of flowrate achieved when applying (2), (3), (4) and (5) (2) to (12) together. (2) Fans: Fans in systems that Subject to (6), fans, other than roof mounted ventilation fans with cowlings, must have a static pressure peak efficiency, determined in accordance with Specification 46, of not more than 200 Pa must have an efficiency at the full load operating point not less than the efficiency calculated with the following formula: than, [formula] In the formula at (a)— where —— [formula] = the minimum required peak system static efficiency for installation type A or C or the minimum required peak system total efficiency for installation type B or D; and [formula] = the static pressure of the system (Pa); and [formula] = natural logarithm. Fans in systems that have a static pressure above 200 Pa must have an efficiency at the full load operating point not less than the efficiency calculated with the following formula: [formula] In the formula at (c)— [formula] = the minimum required system static efficiency for installation type A or C or the minimum required system total efficiency installation type B or D; and [formula] = the motor electrical input power of the fan (kW); (kW) at peak efficiency point, including any integrated motor control equipment; and [formula] = the minimum performance grade obtained from Table … b, obtained from Table J6D5c; and [formula] = natural logarithm. (3) Subject to (6), roof mounted ventilation fans with cowlings must — where the electrical input power of the fan at peak efficiency point, including any integrated motor control equipment, is less than or equal to 30 kW, have peak efficiency, determined in accordance withSpecification 46, of not less than, [formula] where — [formula] = the minimumrequiredsystem static efficiency for installation type A or C or the minimumrequiredsystem total efficiency for installation type B or D; and [formula] = the electrical input power of the fan (kW) at peak efficiency point, including any integrated motor control equipment; and [formula] = natural logarithm; and where the electrical input power of the fan at peak efficiency point, including any integrated motor control equipment, is greater than 30 kW — have a peak system static efficiency of not less than 56% for installation type A or C; or a peak system total efficiency of not less than 56% for installation type B or D. (4) Subject to (6), fans must either — individually, have a fan power ratio, determined in accordance with Specification 46, of less than 0.96; or collectively, have an average fan power ratio, determined in accordance with Specification 46, of less than 0.96. (5) Where a fan’s electrical power input, including any integrated motor control equipment, at the peak efficiency point and full speed, is greater than 750 W — the fan must be capable of variable speed operation; and where serving a single room or space, the fan must be capable of operating at reduced flow when conditions in the room or space served are within the temperature control deadband if applicable; and where serving more than one room or space, the fan and the system it serves must — be capable of variable volume operation; and operate to a variable pressure to the extent practicable. (6) The requirements of (a), (b), (c) and (d) (2) to (5) do not apply to fans — with electrical input power less than or equal to 125 W; or that need to be explosion proof. (3) Ductwork: proof; or that are supply fans inside unitary air-conditioning equipment. (7) The pressure drop in the index run across all straight … be calculated as if the flexible ductwork is laid straight. (8) Flexible ductwork must not account for more than 6 m in total length in any duct run. (9) The upstream connection to ductwork bends, elbows and tees fittings in the index run must have an equivalent diameter to the connected duct. (10) Turning vanes must be included in all rigid ductwork elbows with an angle of 90° 90°, or more acute than 90° 90°, in the index run except where — the inclusion of … long radius bend in accordance with AS 4254.2 is used. (4) Ductwork (11) For ductwork components in the index run: The run — the pressure drop across a coil must not exceed the value specified in Table J6D5d. A J6D5d; and a high efficiency particulate arrestance (HEPA) air filter must not exceed … pressure drop when clean at an air velocity of 1.5 m/s. Any m/s; and any other air filter must not exceed — the pressure drop … pressure drop when clean at an air velocity of 2.5 m/s. The m/s; and the pressure drop across intake louvres, relief louvres and exhaust louvres must not exceed the higher of — for single stage louvres, 30 Pa; and for two … acoustic louvres, 50 Pa; and for other non-weatherproof louvres, 30 Pa. The Pa; and the pressure drop across a variable air volume box, with the … and for other units, 25 Pa not including coil pressure losses. Rooftop losses; and rooftop cowls must not exceed a pressure drop of 30 Pa. Attenuators Pa; and attenuators must not exceed a pressure drop of 40 Pa. Fire Pa; and fire dampers must not exceed a pressure drop of 15 Pa when open. Balancing open; and balancing and control dampers in the index run must not exceed a pressure drop of 25 Pa when in the fully open position. Supply position; and supply air diffusers and grilles must not exceed a pressure drop of 40 Pa. Exhaust Pa; and exhaust grilles must not exceed a pressure drop of 30 Pa. Transfer Pa; and transfer ducts must not exceed a pressure drop of 12 Pa. Door Pa; and door grilles and door undercuts must not exceed a pressure drop of 12 Pa. Active Pa; and active chilled beams must not exceed a pressure drop of 150 Pa. (5) (12) The requirements of (1), (2), (3) and (4) (1) to (11) do not apply to — fans in unducted air-conditioning systems with a supply air capacity of less than 1000 L/s; and fans which are dedicated solely to fire and smoke spill fans, except where also used for air-conditioning or ventilation; control; and the power for process-related components; and kitchen exhaust systems. … Installation type A or C Installation type B or D Axial — All fans as a component of an air handling air-handling unit or fan coil unit 46.0 51.5 61 64 Axial — other 42.0 61.0 40 58 Mixed flow — as a component of an air handling unit or fan coil unit 46.0 51.5 Mixed flow — other 52.5 65.0 50 62 Centrifugal forward — curved 46.0 51.5 forward-curved 44 49 Centrifugal radial bladed 46.0 51.5 44 49 Centrifugal backward-curved 64.0 64.0 61 64 Table Notes Installation type A means an arrangement where the … drop (Pa) 9 55 11 65 13 95 14 110