Table · NCC 2022 Volume One

Table J6D8d Maximum pipework pressure drop – Distributive variable speed systems

Part J6 Air-conditioning and ventilation

Open Table J6D8d on NCC Online ↗
Nominal pipe diameter (mm)Maximum pressure drop in systems operating 5000 hours/annum or less (Pa/m)Maximum pressure drop in systems operating more than 5000 hours/annum (Pa/m)
Not more than 20400250
25400180
32400180
40400180
50400180
65400300
80400300
100400300
125400300
150 or more400300

Table for J6D8 Pump systems

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J6D8d.