Table · NCC 2022 Volume One
Table J6D8c Maximum pipework pressure drop – Distributive constant speed systems
Part J6 Air-conditioning and ventilation
| Nominal pipe diameter (mm) | Maximum pressure drop in systems operating 2000 hours/annum or less (Pa/m) | Maximum pressure drop in systems operating between 2000 hours/annum and 5000 hrs/yr (Pa/m) | Maximum pressure drop in systems operating more than 5000 hours/annum (Pa/m) |
|---|---|---|---|
| Not more than 20 | 400 | 300 | 150 |
| 25 | 400 | 220 | 100 |
| 32 | 400 | 220 | 100 |
| 40 | 400 | 220 | 100 |
| 50 | 400 | 220 | 100 |
| 65 | 400 | 400 | 170 |
| 80 | 400 | 400 | 170 |
| 100 | 400 | 400 | 170 |
| 125 | 400 | 400 | 170 |
| 150 or more | 400 | 400 | 170 |
Table for J6D8 Pump systems
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J6D8c.