Deemed-to-Satisfy Provision · NCC 2022 Volume One

J6D8 Pump systems

Part J6 Air-conditioning and ventilation · NCC 2019: J5.7

Open J6D8 on NCC Online ↗

(1) General — Pumps and pipework that form part of an air-conditioning system must either—

separately comply with (2), (3) and (4); or

achieve a pump motor power per unit of flowrate lower than the pump motor power per unit of flowrate achieved when applying (2), (3) and (4) together.

(2) Circulator pumps — A glandless impeller pump, with a rated hydraulic power output of less than 2.5 kW and that is used in closed loop systems must have an energy efficiency index (EEI) not more than 0.27 calculated in accordance with European Union Commission Regulation No. 622/2012.

(3) Other pumps — Pumps that are in accordance with Articles 1 and 2 of European Union Commission Regulation No. 547/2012 must have a minimum efficiency index (MEI) of 0.4 or more when calculated in accordance with European Union Commission Regulation No. 547/2012.

(4) Pipework — Straight segments of pipework along the index run, forming part of an air-conditioning system—

in pipework systems that do not have branches and have the same flow rate throughout the entire pipe network, must achieve an average pressure drop of not more than—

for constant speed systems, the values nominated in Table J6D8a; or

for variable speed systems, the values nominated in Table J6D8b; or

in any other pipework system, must achieve an average pressure drop of not more than—

for constant speed systems, the values nominated in Table J6D8c; or

for variable speed systems, the values nominated in Table J6D8d.

(5) The requirements of (4) do not apply—

to valves and fittings; or

where the smallest pipe size compliant with (4) results in a velocity of 0.7 m/s or less at design flow.

Table J6D8a Maximum pipework pressure drop – Non-distributive constant speed systems

Nominal pipe diameter (mm)

Maximum pressure drop in systems operating 5000 hours/annum or less (Pa/m)

Maximum pressure drop in systems operating more than 5000 hours/annum (Pa/m)

Not more than 20

400

400

25

400

400

32

400

400

40

400

400

50

400

350

65

400

350

80

400

350

100

400

200

125

400

200

150 or more

400

200

Table J6D8b Maximum pipework pressure drop – Non-distributive variable speed systems

Nominal pipe diameter (mm)

Maximum pressure drop in systems operating 5000 hours/annum or less (Pa/m)

Maximum pressure drop in systems operating more than 5000 hours/annum (Pa/m)

Not more than 20

400

400

25

400

400

32

400

400

40

400

400

50

400

400

65

400

400

80

400

400

100

400

300

125

400

300

150 or more

400

300

Table J6D8c Maximum pipework pressure drop – Distributive constant speed systems

Nominal pipe diameter (mm)

Maximum pressure drop in systems operating 2000 hours/annum or less (Pa/m)

Maximum pressure drop in systems operating between 2000 hours/annum and 5000 hrs/yr (Pa/m)

Maximum pressure drop in systems operating more than 5000 hours/annum (Pa/m)

Not more than 20

400

300

150

25

400

220

100

32

400

220

100

40

400

220

100

50

400

220

100

65

400

400

170

80

400

400

170

100

400

400

170

125

400

400

170

150 or more

400

400

170

Table J6D8d Maximum pipework pressure drop – Distributive variable speed systems

Nominal pipe diameter (mm)

Maximum pressure drop in systems operating 5000 hours/annum or less (Pa/m)

Maximum pressure drop in systems operating more than 5000 hours/annum (Pa/m)

Not more than 20

400

250

25

400

180

32

400

180

40

400

180

50

400

180

65

400

300

80

400

300

100

400

300

125

400

300

150 or more

400

300

Tables

Changed in NCC 2025. See NCC 2025 Volume One J6D8, or show what changed.

(1) General — Pumps and pipework that form part of an air-conditioning system must either — separately comply with (2), (3) (3), (4), (5), (6) and (4); (7); or achieve a pump motor power per unit of flowrate lower than the pump motor power per unit of flowrate achieved when applying (2), (3) (3), (4), (5), (6) and (4) (7) together. (2) Where the pump motor power input at the duty point is greater than 750 W, a pump must be capable of — variable speed operation; and where serving a distributive system — variable volume operation; and variable pressure operation to the extent permitted by — static head requirements; and the requirements of downstream equipment. (3) A distributive system must not have — uncontrolled bypasses; or three port valves. (4) The requirements of (3)(b) do not apply to a distributive system with a single chiller, including a chiller used for space heating, that serves — air-conditioning systems with a total co-incident design load of less than 200 kW; or only one heating coil or one cooling coil. (5) Circulator pumps — A glandless impeller pump, with a rated … calculated in accordance with European Union Commission Regulation No. 622/2012. (3) (6) Other pumps — Pumps that are in accordance with Articles … calculated in accordance with European Union Commission Regulation No. 547/2012. (4) (7) Pipework — Straight segments of pipework along the index run, … average pressure drop of not more than — for constant speed flow systems, the values nominated in Table J6D8a; or for variable speed flow systems, the values nominated in Table J6D8b; or in any … average pressure drop of not more than — for constant speed flow systems, the values nominated in Table J6D8c; or for variable speed flow systems, the values nominated in Table J6D8d. (5) (8) The requirements of (4) (7) do not apply — to valves and fittings; or where the smallest pipe size compliant with (4) (7) results in a velocity of 0.7 m/s or less at design flow. Table J6D8a Maximum pipework pressure drop – Non-distributive constant speed flow systems Nominal pipe diameter (mm) Maximum pressure drop in systems … 200 Table J6D8b Maximum pipework pressure drop – Non-distributive variable speed flow systems Nominal pipe diameter (mm) Maximum pressure drop in systems … 300 Table J6D8c Maximum pipework pressure drop – Distributive constant speed flow systems Nominal pipe diameter (mm) Maximum pressure drop in systems … 170 Table J6D8d Maximum pipework pressure drop – Distributive variable speed flow systems Nominal pipe diameter (mm) Maximum pressure drop in systems … 400 300 125 400 300 150 or more 400 300

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J6D8? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →

Defined terms used