Table · NCC 2022 Volume One
Table S5C11a Type A construction: FRL of loadbearing parts of external walls
Specification 5 Fire-resisting construction
| Distance from a fire-source feature | FRL (in minutes): Structural adequacy/ Integrity / Insulation | |||
|---|---|---|---|---|
| Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 | |
| Less than 1.5 m | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 |
| 1.5 to less than 3 m | 90/60/60 | 120/90/90 | 180/180/120 | 240/240/180 |
| 3 m or more | 90/60/30 | 120/60/30 | 180/120/90 | 240/180/90 |
Table for S5C11 Type A fire-resisting construction — fire-resistance of building elements
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S5C11a.