Table · NCC 2025 Volume One

Table S5C11a Type A construction: FRL of loadbearing parts of external walls

Specification 5 Fire-resisting construction

Open Table S5C11a on NCC Online ↗
Distance from a fire-source featureFRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 partClass 5, 7a or 9Class 6Class 7b or 8
Less than 1.5 m90/90/90120/120/120180/180/180240/240/240
1.5 to less than 3 m90/60/60120/90/90180/180/120240/240/180
3 m or more90/60/30120/60/30180/120/90240/180/90

Table for S5C11 Type A fire-resisting construction — fire-resistance of building elements

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S5C11a.