Table S5C11b Type A construction: FRL of non-loadbearing parts of external walls
Specification 5 Fire-resisting construction
| Distance from a fire-source feature | FRL (in minutes): Structural adequacy / Integrity / Insulation | |||
|---|---|---|---|---|
| Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 | |
| Less than 1.5 m | –/90/90 | –/120/120 | –/180/180 | –/240/240 |
| 1.5 to less than 3 m | –/60/60 | –/90/90 | –/180/120 | –/240/180 |
| 3 m or more | –/–/– | –/–/– | –/–/– | –/–/– |
Table for S5C11 Type A fire-resisting construction — fire-resistance of building elements
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S5C11b.