Table S5C11c Type A construction: FRL of external columns not incorporated in an external wall

Specification 5 Fire-resisting construction

Open Table S5C11c on NCC Online ↗
Column typeFRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 partClass 5, 7a or 9Class 6Class 7b or 8
Loadbearing90/–/–120/–/–180/–/–240/–/–
Non-loadbearing–/–/––/–/––/–/––/–/–

Table for S5C11 Type A fire-resisting construction — fire-resistance of building elements

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S5C11c.