Table · NCC 2022 Volume One
Table S5C11d Type A construction: FRL of common walls and fire walls
Specification 5 Fire-resisting construction
| Wall type | FRL (in minutes): Structural adequacy / Integrity / Insulation | |||
|---|---|---|---|---|
| Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 | |
| Loadbearing or non-loadbearing | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 |
Table for S5C11 Type A fire-resisting construction — fire-resistance of building elements
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S5C11d.