Table S5C11e Type A construction: FRL of loadbearing internal walls
Specification 5 Fire-resisting construction
| Location | FRL (in minutes): Structural adequacy / Integrity / Insulation | |||
|---|---|---|---|---|
| Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 | |
| Fire-resisting lift and stair shafts | 90/90/90 | 120/120/120 | 180/120/120 | 240/120/120 |
| Bounding public corridors, public lobbies and the like | 90/90/90 | 120/–/– | 180/–/– | 240/–/– |
| Between or bounding sole-occupancy units | 90/90/90 | 120/–/– | 180/–/– | 240/–/– |
| Ventilating, pipe, garbage, and like shafts not used for the discharge of hot products of combustion | 90/90/90 | 120/90/90 | 180/120/120 | 240/120/120 |
Table for S5C11 Type A fire-resisting construction — fire-resistance of building elements
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S5C11e.