Table · NCC 2022 Volume One

Table S5C11e Type A construction: FRL of loadbearing internal walls

Specification 5 Fire-resisting construction

Open Table S5C11e on NCC Online ↗
LocationFRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 partClass 5, 7a or 9Class 6Class 7b or 8
Fire-resisting lift and stair shafts90/90/90120/120/120180/120/120240/120/120
Bounding public corridors, public lobbies and the like90/90/90120/–/–180/–/–240/–/–
Between or bounding sole-occupancy units90/90/90120/–/–180/–/–240/–/–
Ventilating, pipe, garbage, and like shafts not used for the discharge of hot products of combustion90/90/90120/90/90180/120/120240/120/120

Table for S5C11 Type A fire-resisting construction — fire-resistance of building elements

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S5C11e.