Table · NCC 2025 Volume One

Table S5C24b Type C construction: FRL of external columns not incorporated into an external wall

Specification 5 Fire-resisting construction

Open Table S5C24b on NCC Online ↗
Distance from a fire-source featureFRL (in minutes): structural adequacy / Integrity / Insulation
Class 2, 3 or 4 partClass 5, 7a or 9Class 6Class 7b or 8
Less than 1.5 m90/–/–90/–/–90/–/–90/–/–
1.5 to less than 3 m–/–/–60/–/–60/–/–60/–/–
3 m or more–/–/––/–/––/–/––/–/–

Table for S5C24 Type C fire-resisting construction — fire-resistance of building elements

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S5C24b.