Performance Requirement · NCC 2022 Volume Three

B1P4 Water efficiency

Part B1 Cold water services · NCC 2019: BP1.2

Open B1P4 on NCC Online ↗

A cold water service must ensure the efficient use of drinking water by—

limiting water usage from—

a tap or outlet for a shower, basin, kitchen sink or laundry trough, to a flow rate of not more than 9 l/m; and

a cistern or flushing device for a urinal, to a flush volume of not more than 2.5 litres for each—

single urinal stall; or

600 mm length of a continuous urinal wall; and

a dual flush cistern or flushing valve that is connected to a water closet pan to a flush volume of not more than—

6 and 3 litres; or

4.5 and 3 litres; or

water saving measures equivalent to or greater than those described in (a).

Applications

The flush volumes of B1P4 may be within a tolerance of—

±0.5 litres for the full flush of a 6/3 litre cistern; or

+0.5 litres for the reduced flush of a 6/3 litre cistern; or

±0.2 litres for a 4.5/3 litre cistern.

Exemptions

The requirements of B1P4 do not apply to a vacuum drainage system.

Changed in NCC 2025. See NCC 2025 Volume Three B1P4, or show what changed.

A means of isolation must be provided to a cold water service must ensure the efficient use of drinking water by — limiting water usage from — a tap and components that require testing, maintenance or outlet for a shower, basin, kitchen sink or laundry trough, to a flow rate of not more than 9 l/m; replacement including mechanical devices, appliances and a cistern or flushing device for a urinal, to a flush volume of not more than 2.5 litres for each — single urinal stall; or 600 mm length of a continuous urinal wall; and a dual flush cistern or flushing valve that is connected to a water closet pan to a flush volume of not more than — 6 and 3 litres; or 4.5 and 3 litres; or water saving measures equivalent to or greater than those described in (a). Applications The flush volumes of B1P4 may be within a tolerance of — ±0.5 litres for the full flush of a 6/3 litre cistern; or +0.5 litres for the reduced flush of a 6/3 litre cistern; or ±0.2 litres for a 4.5/3 litre cistern. Exemptions The requirements of B1P4 do not apply to a vacuum drainage system. controls.

Removed words are struck through; added words are highlighted. Comparison of the text only.