C1P6 Contamination
Part C1 Sanitary plumbing systems · NCC 2019: CP1.1
A sanitary plumbing system must avoid—
entry of water, sewerage and sullage from the system into buildings; and
entry of foul gases from the system into buildings, such that—
at pressures of up to ±375 Pa, water trap seals will not be reduced to depths less than 70 mm for trap seals in pressurised rooms and 25 mm for all other applications; or
an equivalent level of safety to human health is achieved as a system complying to (i); and
entry of surface water, subsurface water and stormwater into the system.
Changed in NCC 2025. See NCC 2025 Volume Three C1P6, or show what changed.
A sanitary plumbing system must avoid — (1) The entry of water, foul gases, sewerage and sullage from the a sanitary plumbing system into buildings; and buildings must be avoided. (2) The entry of foul gases from the a sanitary plumbing system into buildings, buildings must be avoided, such that — at pressures of up to ±375 Pa, … depths less than 70 mm for trap seals in pressurised rooms rooms; and 25 mm for all other applications; or an equivalent level of safety to human health is achieved as a system complying to (i); and with (a). (3) The entry of surface water, subsurface sub-surface water and stormwater into the system. a sanitary plumbing system must be avoided.
Removed words are struck through; added words are highlighted. Comparison of the text only.