Performance Requirement · NCC 2025 Volume Three

C1P5 Ventilation

Part C1 Sanitary plumbing systems · NCC 2019: CP1.1

Open C1P5 on NCC Online ↗

A sanitary plumbing system must ensure that ventilation is provided to avoid hydraulic load imbalance such that—

there is less than a 1% likelihood during the peak hour that when any fixture discharges, air pressure at any trap seal exceeds ±375 Pa difference from atmospheric pressure; or

an equivalent level of safety to human health is achieved as a system complying to (a).

Exemptions

C1P5 Ventilation does not apply to vacuum drainage systems.

Changed since NCC 2022 (minor wording). See NCC 2022 Volume Three C1P5, or show what changed.

A sanitary plumbing system must ensure that ventilation is provided … — there is less than a 1% likelihood during the annual peak hour that when any fixture discharges, air pressure at … Exemptions C1P5 Ventilation does not apply to vacuum drainage systems.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Defined terms used