C1V4 System 3 - Branch design
Part C1 Sanitary plumbing systems
(1) Compliance with C1P5 relating to pipe sizing is verified for each discharge branch when—
each unvented fixture, or combination of fixtures, connects independently to the stack in accordance with Table C1V4a; and
each vented fixture, or combination of fixtures, connects to the stack in accordance with Table C1V4b.
(2) Ventilation requirements must be in accordance with the following:
Each trap vent must be—
not less than DN 50, where the connection of the vent to the branch is liable to blockage due to splashing or submergence; or
DN 32, where the connection of the vent to the branch is not liable to blockage due to splashing or submergence.
Each trap vent connects within 750 mm of the fixture it serves.
Each trap vent must—
terminate at atmosphere or interconnect with another vent in accordance with AS/NZS 3500.2; or
connect to a common trap vent at least 40 mm in diameter; or
connect to the stack above the flood level of the highest fixture; or
terminate to an air admittance valve with a minimum airflow rate equal to 2 times the wastewater design flowrate.
(3) Each branch connection must use a sweep or 45° junction where the branch is—
an equal diameter to the stack; and
the stack is DN 80 or larger.
Table C1V4a System 3 - Unvented fixture connections
Fixture
Waste Nominal Diameter (DN)
Maximum length, in metres (m)
Minimum gradient (%)
Maximum gradient (%)
Maximum number of bends
Maximum vertical drop, in metres (m)
Basin
32
1.7
2.2
2.2
0
0
Basin
32
1.1
4.4
4.4
0
0
Basin
32
0.7
8.7
8.7
0
0
Basin
40
3
1.8
4.4
2
0
Basin group ≤4 basins
50
4
1.8
4.4
0
0
Bidet
32
1.7
2.2
2.2
0
0
Bidet
32
1.1
4.4
4.4
0
0
Bidet
32
0.7
8.7
8.7
0
0
Bidet
40
3
1.8
4.4
2
0
Shower
40
No limit
1.8
9
No limit
1.5
Bath
40
No limit
1.8
9
No limit
1.5
Single urinal
40
3
1.8
9
No limit
1.5
Slab urinal
65
3
1.8
9
No limit
1.5
Sink - kitchen
40
No limit
1.8
9
No limit
1.5
Trough - laundry
40
3
1.8
9
No limit
1.5
Domestic dishwasher
40
3
1.8
4.4
No limit
1.5
Domestic clothes washing machine - up to 6 kg
40
3
1.8
4.4
No limit
1.5
Water closet
80
No limit
1.8
No limit
No limit
1.5
Water closet
100
No limit
1.8
No limit
No limit
1.5
Water closet group ≤8 water closets
100
15
0.9
9
2
1.5
Food waste disposal unit
40
3
13.5
No limit
No limit
1.5
Sanitary napkin disposal unit
40
3
5.4
No limit
No limit
1.5
Floor waste gully
50
No limit
1.8
No limit
No limit
1.5
Floor waste gully
80
No limit
1.8
No limit
No limit
1.5
Floor waste gully
100
No limit
1.8
No limit
No limit
1.5
Table C1V4b System 3 - Vented fixture connections
Fixture
Waste Nominal Diameter (DN)
Maximum length, in metres (m)
Minimum gradient (%)
Maximum gradient (%)
Maximum number of bends
Maximum vertical drop, in metres (m)
Basin
32
3
1.8
No limit
2
3
Basin
40
3
1.8
No limit
No limit
3
Basin group ≤5 basins
50
7
1.8
4.4
No limit
No limit
Basin group ≤10 basins
50
10
1.8
4.4
No limit
No limit
Bidet
32
3
1.8
No limit
2
3
Bidet
40
3
1.8
No limit
No limit
3
Shower
40
No limit
1.8
No limit
No limit
No limit
Bath
40
No limit
1.8
No limit
No limit
No limit
Single urinal
40
3
1.8
No limit
No limit
3
>1 Single urinal
50
No limit
1.8
No limit
No limit
No limit
Trough urinal
50
3
1.8
No limit
No limit
3
Slab urinal
65
3
1.8
No limit
No limit
3
Sink - kitchen
40
No limit
1.8
No limit
No limit
No limit
Trough - laundry
40
3
1.8
No limit
No limit
No limit
Domestic dishwasher
40
No limit
1.8
No limit
No limit
No limit
Domestic clothes washing machine (up to 6 kg)
40
No limit
1.8
No limit
No limit
No limit
Water closet
80
No limit
1.8
No limit
No limit
No limit
Water closet
100
No limit
1.8
No limit
No limit
No limit
Water closet group ≤8
100
15
0.9
No limit
No limit
No limit
Food waste disposal unit
40
3
13.5
No limit
No limit
3
Sanitary napkin disposal unit
40
3
5.4
No limit
No limit
3
Floor waste gully
50
No limit
1.8
No limit
No limit
No limit
Floor waste gully
80
No limit
1.8
No limit
No limit
No limit
Floor waste gully
100
No limit
1.8
No limit
No limit
No limit
Small potato peeler
40
3
13.5
No limit
No limit
3
Limitations
The maximum number of bends permitted is measured from the fixture trap weir to the connection to the stack, excluding the first bend after the trap weir.
The maximum pipe length is measured from the fixture trap weir to the connection to the stack.
A slab urinal must not cater for more than 7 people. Additional waste outlets may be required for longer urinals.
Where a water closet is connected, sweep or 45º junctions must be used to connect to the stack.
Bottle and resealing traps are not permitted for food waste disposal units or sanitary napkin disposal units.
Tables
- Table C1V4a System 3 - Unvented fixture connections
- Table C1V4b System 3 - Vented fixture connections