Verification Method · NCC 2022 Volume Three

C1V4 System 3 - Branch design

Part C1 Sanitary plumbing systems

Open C1V4 on NCC Online ↗

(1) Compliance with C1P5 relating to pipe sizing is verified for each discharge branch when—

each unvented fixture, or combination of fixtures, connects independently to the stack in accordance with Table C1V4a; and

each vented fixture, or combination of fixtures, connects to the stack in accordance with Table C1V4b.

(2) Ventilation requirements must be in accordance with the following:

Each trap vent must be—

not less than DN 50, where the connection of the vent to the branch is liable to blockage due to splashing or submergence; or

DN 32, where the connection of the vent to the branch is not liable to blockage due to splashing or submergence.

Each trap vent connects within 750 mm of the fixture it serves.

Each trap vent must—

terminate at atmosphere or interconnect with another vent in accordance with AS/NZS 3500.2; or

connect to a common trap vent at least 40 mm in diameter; or

connect to the stack above the flood level of the highest fixture; or

terminate to an air admittance valve with a minimum airflow rate equal to 2 times the wastewater design flowrate.

(3) Each branch connection must use a sweep or 45° junction where the branch is—

an equal diameter to the stack; and

the stack is DN 80 or larger.

Table C1V4a System 3 - Unvented fixture connections

Fixture

Waste Nominal Diameter (DN)

Maximum length, in metres (m)

Minimum gradient (%)

Maximum gradient (%)

Maximum number of bends

Maximum vertical drop, in metres (m)

Basin

32

1.7

2.2

2.2

0

0

Basin

32

1.1

4.4

4.4

0

0

Basin

32

0.7

8.7

8.7

0

0

Basin

40

3

1.8

4.4

2

0

Basin group ≤4 basins

50

4

1.8

4.4

0

0

Bidet

32

1.7

2.2

2.2

0

0

Bidet

32

1.1

4.4

4.4

0

0

Bidet

32

0.7

8.7

8.7

0

0

Bidet

40

3

1.8

4.4

2

0

Shower

40

No limit

1.8

9

No limit

1.5

Bath

40

No limit

1.8

9

No limit

1.5

Single urinal

40

3

1.8

9

No limit

1.5

Slab urinal

65

3

1.8

9

No limit

1.5

Sink - kitchen

40

No limit

1.8

9

No limit

1.5

Trough - laundry

40

3

1.8

9

No limit

1.5

Domestic dishwasher

40

3

1.8

4.4

No limit

1.5

Domestic clothes washing machine - up to 6 kg

40

3

1.8

4.4

No limit

1.5

Water closet

80

No limit

1.8

No limit

No limit

1.5

Water closet

100

No limit

1.8

No limit

No limit

1.5

Water closet group ≤8 water closets

100

15

0.9

9

2

1.5

Food waste disposal unit

40

3

13.5

No limit

No limit

1.5

Sanitary napkin disposal unit

40

3

5.4

No limit

No limit

1.5

Floor waste gully

50

No limit

1.8

No limit

No limit

1.5

Floor waste gully

80

No limit

1.8

No limit

No limit

1.5

Floor waste gully

100

No limit

1.8

No limit

No limit

1.5

Table C1V4b System 3 - Vented fixture connections

Fixture

Waste Nominal Diameter (DN)

Maximum length, in metres (m)

Minimum gradient (%)

Maximum gradient (%)

Maximum number of bends

Maximum vertical drop, in metres (m)

Basin

32

3

1.8

No limit

2

3

Basin

40

3

1.8

No limit

No limit

3

Basin group ≤5 basins

50

7

1.8

4.4

No limit

No limit

Basin group ≤10 basins

50

10

1.8

4.4

No limit

No limit

Bidet

32

3

1.8

No limit

2

3

Bidet

40

3

1.8

No limit

No limit

3

Shower

40

No limit

1.8

No limit

No limit

No limit

Bath

40

No limit

1.8

No limit

No limit

No limit

Single urinal

40

3

1.8

No limit

No limit

3

>1 Single urinal

50

No limit

1.8

No limit

No limit

No limit

Trough urinal

50

3

1.8

No limit

No limit

3

Slab urinal

65

3

1.8

No limit

No limit

3

Sink - kitchen

40

No limit

1.8

No limit

No limit

No limit

Trough - laundry

40

3

1.8

No limit

No limit

No limit

Domestic dishwasher

40

No limit

1.8

No limit

No limit

No limit

Domestic clothes washing machine (up to 6 kg)

40

No limit

1.8

No limit

No limit

No limit

Water closet

80

No limit

1.8

No limit

No limit

No limit

Water closet

100

No limit

1.8

No limit

No limit

No limit

Water closet group ≤8

100

15

0.9

No limit

No limit

No limit

Food waste disposal unit

40

3

13.5

No limit

No limit

3

Sanitary napkin disposal unit

40

3

5.4

No limit

No limit

3

Floor waste gully

50

No limit

1.8

No limit

No limit

No limit

Floor waste gully

80

No limit

1.8

No limit

No limit

No limit

Floor waste gully

100

No limit

1.8

No limit

No limit

No limit

Small potato peeler

40

3

13.5

No limit

No limit

3

Limitations

The maximum number of bends permitted is measured from the fixture trap weir to the connection to the stack, excluding the first bend after the trap weir.

The maximum pipe length is measured from the fixture trap weir to the connection to the stack.

A slab urinal must not cater for more than 7 people. Additional waste outlets may be required for longer urinals.

Where a water closet is connected, sweep or 45º junctions must be used to connect to the stack.

Bottle and resealing traps are not permitted for food waste disposal units or sanitary napkin disposal units.