Table C1V1a Frequency factors
Part C1 Sanitary plumbing systems
| Fixture usage | NCC building classes | Frequency factor (K) |
|---|---|---|
| Intermittent use e.g. dwelling, guesthouse or office | Class 1, Class 2, Class 3 or Class 4 | 0.5 |
| Frequent use e.g. hospital, restaurant or hotel | Class 5, Class 6, Class 7, Class 8, Class 9a or Class 9c | 0.7 |
| Congested use e.g. open to general public, school | Class 9b | 1.0 |
| Special use e.g. laboratory | Not applicable | 1.2 |
Table for C1V1 Determination of sanitary plumbing wastewater flowrates
Changed in NCC 2025. See NCC 2025 Volume Three Table C1V1a, or show what changed.
Fixture usage NCC building class | NCC building classes class example | Frequency factor (K) Intermittent | Time interval between fixture use e.g. averaged over peak period (s) Class 1 | Residential dwelling, guesthouse duplexes, or office townhouses | 0.5 | 1200 Class 1, Class 2, 2 | Apartment or unit | 0.5 - 0.8 | 450 - 1200 Class 3 or | Hotel, hostel, dormitory | 0.6 - 0.8 | 450 - 800 Class 4 | Sole dwelling within a Class 5-9 building | 0.5 Frequent use e.g. hospital, restaurant or hotel | 1200 Class 5, 5 | Office | 0.6 - 0.8 | 450 - 800 Class 6, 6 | Retail, shop, restaurant, café | 0.6 - 0.8 | 450 - 800 Class 7, 7 | Carpark, warehouse, storage building | 0.6 - 0.8 | 450 - 800 Class 8, 8 | Factory, workshop, laboratory | 0.6 - 0.8 | 450 - 800 Class 9a or | Healthcare building, hospital, and GP clinics | 0.6 - 0.8 | 450 - 800 Class 9b | Public event buildings, stadiums, theatres, schools, universities, and churches | 1.0 - 1.2 | 200 - 300 Class 9c | 0.7 Congested use e.g. open to general public, school Aged care facilities | Class 9b 0.6 - 0.8 | 1.0 Special use e.g. laboratory | Not applicable | 1.2 450 - 800
Removed words are struck through; added words are highlighted. Comparison of the text only.