Table C1V1a Frequency factors

Part C1 Sanitary plumbing systems

Open Table C1V1a on NCC Online ↗
Fixture usageNCC building classesFrequency factor (K)
Intermittent use e.g. dwelling, guesthouse or officeClass 1, Class 2, Class 3 or Class 40.5
Frequent use e.g. hospital, restaurant or hotelClass 5, Class 6, Class 7, Class 8, Class 9a or Class 9c0.7
Congested use e.g. open to general public, schoolClass 9b1.0
Special use e.g. laboratoryNot applicable1.2

Table for C1V1 Determination of sanitary plumbing wastewater flowrates

Changed in NCC 2025. See NCC 2025 Volume Three Table C1V1a, or show what changed.

Fixture usage NCC building class | NCC building classes class example | Frequency factor (K) Intermittent | Time interval between fixture use e.g. averaged over peak period (s) Class 1 | Residential dwelling, guesthouse duplexes, or office townhouses | 0.5 | 1200 Class 1, Class 2, 2 | Apartment or unit | 0.5 - 0.8 | 450 - 1200 Class 3 or | Hotel, hostel, dormitory | 0.6 - 0.8 | 450 - 800 Class 4 | Sole dwelling within a Class 5-9 building | 0.5 Frequent use e.g. hospital, restaurant or hotel | 1200 Class 5, 5 | Office | 0.6 - 0.8 | 450 - 800 Class 6, 6 | Retail, shop, restaurant, café | 0.6 - 0.8 | 450 - 800 Class 7, 7 | Carpark, warehouse, storage building | 0.6 - 0.8 | 450 - 800 Class 8, 8 | Factory, workshop, laboratory | 0.6 - 0.8 | 450 - 800 Class 9a or | Healthcare building, hospital, and GP clinics | 0.6 - 0.8 | 450 - 800 Class 9b | Public event buildings, stadiums, theatres, schools, universities, and churches | 1.0 - 1.2 | 200 - 300 Class 9c | 0.7 Congested use e.g. open to general public, school Aged care facilities | Class 9b 0.6 - 0.8 | 1.0 Special use e.g. laboratory | Not applicable | 1.2 450 - 800

Removed words are struck through; added words are highlighted. Comparison of the text only.

Defined terms used