Verification Method · NCC 2022 Volume Three

C1V1 Determination of sanitary plumbing wastewater flowrates

Part C1 Sanitary plumbing systems

Open C1V1 on NCC Online ↗

(1) Compliance with C1P3 for pipe sizing is verified for each sanitary plumbing pipework section when the discharge flowrate is not less than the greater of—

the probable simultaneous wastewater flowrate calculated in accordance with (2); or

the Discharge Unit (DU) value of the highest fixture connected upstream of the pipework section as given in Table C1V1b, in litres per second.

(2) For the purposes of (1)(a), for each pipework section, the design probable simultaneous wastewater flowrate must be calculated in accordance with the following:

[formula] (3) In the equation shown at (2)—

[formula] = the probable simultaneous wastewater flowrate for that pipework section (l/s); and

[formula] = the sum of any other wastewater flowrates such as pumped discharges (l/s); and

[formula] = the frequency factor given in Table C1V1a (dimensionless); and

[formula] = the sum of the discharge units as given in Table C1V1b, connected upstream of that pipework section (dimensionless).

Table C1V1a Frequency factors

Fixture usage

NCC building classes

Frequency factor (K)

Intermittent use e.g. dwelling, guesthouse or office

Class 1, Class 2, Class 3 or Class 4

0.5

Frequent use e.g. hospital, restaurant or hotel

Class 5, Class 6, Class 7, Class 8, Class 9a or Class 9c

0.7

Congested use e.g. open to general public, school

Class 9b

1.0

Special use e.g. laboratory

Not applicable

1.2

Table C1V1b Discharge units

Fixture

System 1

System 2

System 3

Basin

0.5

0.3

0.3

Shower

0.6

0.4

0.4

Urinal

0.8

0.5

0.4

Bath

0.8

0.6

1.3

Kitchen sink

0.8

0.6

1.3

Water closet

2.0

1.8

1.2

Washing machine - up to 6 kg

0.8

0.6

0.6

Domestic dishwasher

0.8

0.6

0.2

Tables

Changed in NCC 2025. See NCC 2025 Volume Three C1V1, or show what changed.

(1) Compliance with C1P3 for pipe sizing is verified for … upstream of that pipework section (dimensionless). Table C1V1a Frequency factors Fixture usage NCC building classes class NCC building class example Frequency factor (K) Intermittent Time interval between fixture use e.g. averaged over peak period (s) Class 1 Residential dwelling, guesthouse duplexes, or office townhouses 0.5 1200 Class 1, Class 2, 2 Apartment or unit 0.5 - 0.8 450 - 1200 Class 3 or Hotel, hostel, dormitory 0.6 - 0.8 450 - 800 Class 4 Sole dwelling within a Class 5-9 building 0.5 Frequent use e.g. hospital, restaurant or hotel 1200 Class 5, 5 Office 0.6 - 0.8 450 - 800 Class 6, 6 Retail, shop, restaurant, café 0.6 - 0.8 450 - 800 Class 7, 7 Carpark, warehouse, storage building 0.6 - 0.8 450 - 800 Class 8, 8 Factory, workshop, laboratory 0.6 - 0.8 450 - 800 Class 9a or Healthcare building, hospital, and GP clinics 0.6 - 0.8 450 - 800 Class 9b Public event buildings, stadiums, theatres, schools, universities, and churches 1.0 - 1.2 200 - 300 Class 9c 0.7 Congested use e.g. open to general public, school Class 9b 1.0 Special use e.g. laboratory Not applicable 1.2 Aged care facilities 0.6 - 0.8 450 - 800 Table C1V1b Discharge units Fixture System 1 System 2 System 3 Discharge Units (DU) Basin 0.3 Bath (with shower) 0.5 0.3 Bath (without shower) 0.6 Bidet 0.3 Shower 0.6 0.4 (single) 0.4 Urinal 0.8 (wall-hung) 0.5 0.4 Bath 0.8 0.6 1.3 Urinal (stall for each 600 mm length of slab) 0.2 Kitchen sink 0.8 0.6 1.3 Water closet 2.0 (6L cistem) 1.8 1.2 Water closet (4L cistem) 1.8 Washing machine - up to 6 kg 0.8 0.6 0.6 Domestic dishwasher 0.8 0.6 0.2 Floor waste gully Sum of DU from connected fixtures

Removed words are struck through; added words are highlighted. Comparison of the text only.

Clauses referred to

Defined terms used