H6P2 Energy usage
Part H6 Energy efficiency · NCC 2019: NSW P2.6.1(b), P2.6.2
(1) The energy value of a building’s domestic services must not exceed 70% of the energy value with—
a 3-star ducted heat pump, rated under the 2019 GEMS determination, heating all spaces that are provided with heating; and
a 3-star ducted heat pump, rated under the 2019 GEMS determination, cooling all spaces that are provided with cooling; and
a 5-star instantaneous gas water heater, rated under the 2017 GEMS determination, providing all domestic hot water; and
a lighting power density of 4 W/m2 serving all internal spaces that are provided with artificial lighting.
(2) Domestic services, including any associated distribution system and components must, to the degree necessary, have features that facilitate the efficient use of energy appropriate to—
the domestic service and its usage; and
the geographic location of the building; and
the location of the domestic service; and
the energy source.