Queensland variation · ABCB Housing Provisions 2025

QLD 3.4.1 Requirements for termite management systems

QLD Part 3.4 Termite risk management · varies 3.4.1 Requirements for termite management systems

Open on NCC Online ↗

Insert QLD subclause 3.4.1(3) in clause 3.4.1 as follows:

(3) A termite management system installed in a Class 1 or 10 building minimise the risk of termite attack to primary building elements shall be in accordance with clause 3.4.2.

Insert QLD subclause 3.4.1(4) in clause 3.4.1 as follows:

(4) The termite management system required by (3) must have—

for a non-temporary Class 1 building, a design life of at least 50 years; or

for other than a non-temporary Class 1 building, a design life of at least 50 years or the specified design life of the building, whichever is the lesser.

Insert QLD subclause 3.4.1(5) in clause 3.4.1 as follows:

(5) A termite management system need not comply with (4) if it is easily and readily accessible for replenishment or replacement and is capable of being replenished or replaced.

Insert QLD subclause 3.4.1(6) in clause 3.4.1 as follows:

(6) Where a chemical is used as an external perimeter termite management system, it must be—

installed by excavating trenches, treating the exposed trench and backfilling the trench with treated material; and

covered by a concrete cover strip not less than 50 mm thick and 300 mm wide measured from the external wall of the building.

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 QLD 3.4.1.