Table 4.2.20d Localised thickening under concentrated load — timber floor and metal roof — roof load area = 0 m2

Part 4.2 Footings, slabs and associated elements

Open Table 4.2.20d on NCC Online ↗
Localised thickeningMaximum floor load area (m2)
41016
Square thickening size (mm)400 x 400600 x 600750 x 750
Thickening depth (mm)250300350

Table Notes

Load accounted for includes 0.53 kPa permanent timber floor, 0.4 kPa permanent metal roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations included are G + 0.5Q for ULS.

Minimum bearing pressure is 1000 kPa for pad footings.

A roof load area of “0” must be used for footings not supporting roof loads.

The length of wall allowed for is equal to the square root of the floor area.

Table for 4.2.20 Concentrated loads