Table · ABCB Housing Provisions 2025
Table 6.3.3b Maximum bearer span (m) — continuous span — bearer supporting timber floor and 3 m high non-loadbearing internal wall
Part 6.3 Structural steel members
| Steel section | Effective load width (m) | ||||
|---|---|---|---|---|---|
| 1.8 | 2.4 | 3.0 | 3.6 | 4.2 | |
| 125 TFB | 5.2 | 4.6 | 4.2 | 3.9 | 3.6 |
| 180 UB 16.1 | 6.8 | 6.0 | 5.5 | 5.1 | 4.7 |
| 200 UB 18.2 | 7.7 | 6.9 | 6.2 | 5.8 | 5.4 |
| 250 UB 25.7 | 10.2 | 9.1 | 8.3 | 7.6 | 7.1 |
| 250 x 150 x 9 RHS | 12.4 | 11.5 | 10.5 | 9.8 | 9.1 |
| 250 x 150 x 5 RHS | 9.5 | 8.4 | 7.7 | 7.1 | 6.6 |
| 310 UB 32.0 | 12.3 | 11.0 | 10.0 | 9.2 | 8.6 |
| 125 x 75 x 2 RHS | 2.9 | 2.6 | 2.3 | 2.2 | 2.0 |
| 125 x 75 x 3 RHS | 4.0 | 3.5 | 3.2 | 2.9 | 2.7 |
| 150 x 50 x 2 RHS | 3.3 | 2.9 | 2.6 | 2.4 | 2.3 |
| 150 x 50 x 3 RHS | 4.2 | 3.7 | 3.4 | 3.1 | 2.9 |
| 100 TFB | 3.4 | 3.0 | 2.7 | 2.5 | 2.4 |
| 150 PFC | 6.5 | 5.8 | 5.3 | 4.9 | 4.6 |
| 180 PFC | 7.8 | 6.9 | 6.3 | 5.8 | 5.4 |
| 200 PFC | 8.5 | 7.6 | 6.9 | 6.4 | 5.9 |
| 250 PFC | 11.6 | 10.4 | 9.5 | 8.7 | 8.2 |
| 300 PFC | 13.4 | 12.0 | 10.9 | 10.1 | 9.4 |
Table Notes
Load accounted for includes 0.53 kPa permanent floor, 0.92 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed.
Load combinations included are 1.35G and 1.25G+1.5Q for ULS and G + 0.7Q for SLS with a maximum deflection of span/300.
Bearers are assumed to have intermediate lateral restraints at joist locations and are considered fully laterally restrained.
Table for 6.3.3 Bearers
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 6.3.3b.