Table 7.5.4a Stud and fixing spacings for 6 mm fibre-cement sheet wall cladding
Part 7.5 Timber and composite wall cladding
| Wind class | Maximum stud spacing (mm) | Maximum nail spacing within 1.2 m of the external corners of the building (mm) Note 1 | Maximum nail spacing elsewhere (mm) Note 1 |
|---|---|---|---|
| N1 | ≤ 1.2 m of external building corners: 600 Elsewhere: 600 | Body: 300, Edges: 200 | Body: 300, Edges: 200 |
| N2 | ≤ 1.2 m of external building corners: 600 Elsewhere: 600 | Body: 200, Edges: 200 | Body: 300, Edges: 200 |
| N3 | ≤ 1.2 m of external building corners: 450 Elsewhere: 600 | Body: 200, Edges: 200 | Body: 200, Edges: 200 |
Table Notes
Maximum nail spacing using 2.8 mm fibre-cement nails.
Fixings must be located not less than 50 mm from the edge of all corners.
Fasteners must penetrate not less than 30 mm into a timber frame.
Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.
Table for 7.5.4 Sheet wall cladding
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 7.5.4a.