B1V1 Determination of velocity
(1)
Compliance with Performance Requirement B1P2 is verified for a cold-water service in a Class 2 or Class 3 building when the pipework diameter of that service is greater than or equal to the minimum diameter ( [formula] ) determined in accordance with the following equation:
[formula] when: [formula] where—
[formula] represents the minimum pipe diameter (mm); and
[formula] represents the 99th percentile flow rate (L/s); and
[formula] represents the maximum velocity (m/s).
(2) The flow rate must be calculated by determining the greater of—
probable simultaneous flow rate in accordance with (3); or
flow rate of a single fixture with the largest flow rate downstream of the pipework section.
(3) For a specific pipe section, the probable simultaneous flow rate must be calculated in accordance with the following equation:
[formula] where—
[formula] represents the 99th percentile flow rate (i.e. the designed probable simultaneous flow rate); and
[formula] represents the probability of stagnation during peak usage (zero demand) determined in accordance with (4); and
[formula] represents the total number of fixture groups; and
[formula] represents the index of individual fixture groups; and
[formula] is the number of fixtures for a specific fixture group downstream of a pipework section; and
[formula] is the specific fixture flow rate; and
[formula] is the probability of fixture use (probability that a fixture group is running water during the peak period of water consumption) determined in accordance with (5); and
[formula] represents the 99th percentile of the standard normal distribution and is equal to 2.362.
(4) The probability of stagnation during peak usage must be determined in accordance with the following equation:
[formula] where—
[formula] represents the probability of stagnation during peak usage (zero demand); and
[formula] represents the total number of fixture groups; and
[formula] represents the index of individual fixture groups; and
[formula] is the number of fixtures for a specific fixture group downstream of the pipework section; and
[formula] is the probability of fixture use (probability that a fixture group is running water during the peak period of water consumption) determined in accordance with (5).
(5) The probability of fixture use must be calculated in accordance with the following equation:
[formula] where—
[formula] represents the probability of fixture use; and
[formula] is the baseline probability of fixture use determined in accordance with (6); and
[formula] represents the probability adjustment factor according to occupancy calculated in accordance with (7).
(6) The baseline probability of fixture use must be determined in accordance with the following:
[formula] when: [formula] when: [formula] when: [formula] where—
[formula] is the baseline probability of fixture use; and
[formula] represents the number of apartments drawing water downstream of the pipe section; and
[formula] are coefficients from Table B1V1.
(7) The probability adjustment factor must be determined in accordance with the following:
[formula] where—
[formula] represents the probability adjustment factor according to occupancy; and
[formula] represents the number of apartments drawing water downstream of the pipe section; and
[formula] represents the estimated total number of building occupants drawing water downstream of the pipe section; and
[formula] represents the increased probability of fixture use per additional building occupant over [formula] calculated in accordance with (8).
(8)
The increased probability of fixture use per additional building occupant over [formula] must be determined in accordance with the following:
[formula] when [formula] where—
[formula] represents the increased probability of fixture use per additional building occupant over [formula] ; and
[formula] represents the number of apartments drawing water downstream of the pipe section; and
[formula] are coefficients from Table B1V1.
Table B1V1 Fixture probability coefficients
Fixture
[formula] |
[formula] |
[formula] |
[formula] |
[formula] | Shower
0.061
0.908
-0.475
0.020
-1.343
Tap
0.009
1
0
0.004
-0.880
Toilet
0.002
1
0
0.002
-0.880
Washing machine
0.031
0.976
-0.515
0.005
-1.349
Dishwasher
0.001
1
0
0.0005
-0.880
Bath
0.006
1.460
-0.411
0.008
-1.768
Table Notes
The probability coefficient [formula] for taps is for all locations (e.g. kitchen, laundry and bathroom).