New South Wales variation · NCC 2025 Volume Three

NSW B5D2 Drinking water service

NSW Part B5 Cross-connection control · varies B5D2 Drinking water service

Open on NCC Online ↗

Delete clause B5D2 and insert NSW B5D2 as follows:

(1) A hazard exists wherever it is possible for water or contaminants to enter a drinking water service or supply via any potential or actual cross-connection between—

The drinking water service; and

Any of the following:

A non-drinking water service.

A rainwater service.

An alternative water supply,.

A swimming pool.

Pipes, fixtures or specialist equipment (including boilers and pumps) containing chemicals, liquids, gases or other substances which may be harmful to health or safety.

(2) Each hazard must—

Be assigned—

an Individual protection Hazard Rating in accordance with B5D7(4), (5),or (6); or

a Zone protection Hazard Rating in accordance with B5D7(7), (8), (9); and

Be isolated from the drinking water service by an appropriate backflow prevention device which is selected and installed in accordance with Section 4 of AS/NZS 3500.1.

(3) Where a site is served by a Network Utility Operator’s drinking water, appropriate containment protection must be:

selected and installed in accordance with the Network Utility Operators relevant regulations, guidelines, policies or similar documents; or

where the Network Utility Operator does not prescribe requirements for containment protection, assign a Containment protection Hazard Rating in accordance with B5D7 (10), (11) or (12), and select and install appropriate containment protection in accordance with Section 4 of AS/NZS 3500.1

New in NCC 2025. No NSW B5D2 in NCC 2022 Volume Three; it may have moved or been renumbered.

The national clause