Performance Requirement · NCC 2025 Volume Three

C2P4 Ventilation

Part C2 Sanitary drainage systems · NCC 2019: CP2.1

Open C2P4 on NCC Online ↗

(1) A sanitary drainage system must ensure there is adequate ventilation to avoid foul air and gases accumulating in the sanitary drainage and sewerage system.

(2) A sanitary drainage system must ensure that ventilation is provided to avoid hydraulic load imbalance such that—

there is less than a 1% likelihood during the peak hour that when any fixture discharges, air pressure at any trap seal exceeds ±375 Pa difference from atmospheric pressure; or

an equivalent level of safety to human health is achieved as a system complying to (a).

Changed since NCC 2022 (minor wording). See NCC 2022 Volume Three C2P4, or show what changed.

(1) A sanitary drainage system must ensure there is adequate … — there is less than a 1% likelihood during the annual peak hour that when any fixture discharges, air pressure at … human health is achieved as a system complying to (a).