Performance Requirement · NCC 2025 Volume Three

C2P5 Contamination

Part C2 Sanitary drainage systems · NCC 2019: CP2.1

Open C2P5 on NCC Online ↗

(1) The entry of water, foul gases, sewerage and sullage from a sanitary drainage system into buildings must be avoided.

(2) A sanitary drainage system must be protected against internal contamination.

(3) The entry of foul gases from a sanitary drainage system into buildings must be avoided, such that—

at pressures of up to ±375 Pa, water trap seals will not be reduced to depths less than—

70 mm for trap seals in pressurised rooms; and

25 mm for all other applications; or

an equivalent level of safety to human health is achieved as a system complying to (a).

(4) The entry of surface water, sub-surface water and stormwater into a sanitary drainage system must be avoided.

Changed since NCC 2022. See NCC 2022 Volume Three C2P5, or show what changed.

(1) A The entry of water, foul gases, sewerage and sullage from a sanitary drainage system into buildings must ensure protection against internal contamination. be avoided. (2) A sanitary drainage system must avoid the be protected against internal contamination. (3) The entry of water, foul air and gases from the system into buildings. (3) A a sanitary drainage system into buildings must avoid the be avoided, such that — at pressures of up to ±375 Pa, water trap seals will not be reduced to depths less than — 70 mm for trap seals in pressurised rooms; and 25 mm for all other applications; or an equivalent level of safety to human health is achieved as a system complying to (a). (4) The entry of surface water, sub-surface water and stormwater into the system. a sanitary drainage system must be avoided.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Defined terms used